WALL MOUNT GAS-FIRED WATER BOILER — Boiler Manual
Figure 1482EMOVALOFmATPLATEHEATEXCHANGER
SCREWONLEFTSIDE
33 Maintenance (continued)
&IGURE0RESSURERELEASEFORDOMESTICWATERCIRCUIT
#OMBI/NLY
3YSTEMSUPPLY
$OMESTICHOTWATEROUTLET
3 Gas inlet
$OMESTICCOLDWATERINLET
3YSTEMRETURN
6
0RESSURERELIEFSCREW
1
2
3
4
5
6
4. #LOSETHEVALVEOF#(SYSTEMSUPPLYANDRETURNPLACED
BEFORETHEBOILERCONNECTIONS
5. 2ELEASETHEPRESSUREOF#(CIRCUITBYLOOSINGTHEPLASTICSCREW
placed next to the CH return (5), see Figure 144.
Release Heat Exchanger pressure in the boiler by
LOOSINGTHEPLASTICSCREWOFTHEPUMPPLACEDNEXT
to heat exchanger return.
6. Remove the two (2) screws securing the plate heat exchanger
to the diverter valve and to the DHW inlet.
7. 0ULLOUTTHEmATPLATEHEATEXCHANGERPULLINGOUTANDUPFROM
THEREAROFTHEBOILER
e direction of arrows on heat exchanger.
e
brazed plate heat exchanger must be rein-
stalled in the same orientation.
4HENEXTTWOlGURESAREFORILLUSTRATINGAND
information only.
The gas valve does NOT need to be removed to
replace brazed plate heat exchanger
8. Flat plate heat exchanger can be immersed in a chemical
cleaning bath.
9. The treatment time must be chosen according to the amount
OFSCALEDEPOSITSPRESENTINTHEEXCHANGERANDHOWEVERSUCH
time must always be less than the maximum treatment time
SPECIlEDBYTHEMANUFACTURERONTHEPRODUCTDATASHEET
DHW returns
(diverter valve)
DHW inlet
Figure 1492EMOVALOFmATPLATEHEATEXCHANGER
SCREWONRIGHTSIDE
Figure 1502EINSTALLTHEFOURGASKETSINTO$(7INLETS
ANDRETURNSCOMPONENTSREMOVEDTOSHOW
GASKETLOCATIONSFORILLUSTRATINGPURPOSES