EasyManua.ls Logo

Freestyle 80 - DIRECT VENT - Sidewall Concentric

Freestyle 80
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Part number 550-142-850/0716
25
FreeStyle
®
WALL MOUNT GAS-FIRED WATER BOILERBoiler Manual
11 DIRECT VENT — Sidewall concentric
Allowable vent/air pipe materials
& lengths
1. The concentric termination kit must be purchased
separately.
Use only the vent materials and kits listed in
Figure 21, page 19
0ROVIDEPIPEADAPTERSIF
specified.
2. Locate the termination such that the total air pip-
INGANDVENTPIPINGFROMTHEBOILERTOTHETERMINA-
tion will not exceed the maximum length given in
Figure 20, page 18
.
3. This termination requires a 45-degree elbow that is
not supplied with the termination kit. The maximum
VENTAIRPIPELENGTHSINCLUDEALLOWANCEFORTHISELBOW
For polypropylene applications, comply
with any additional requirements in the
VENTSYSTEMMANUFACTURERSINSTRUCTIONS
(Do Not use 3” PVC transition pieces at the
boiler vent and air connections)
and at the
TERMINATIONIFUSING A v 06# CONCENTRIC
vent kit. Install a locking collar at every joint.
&OR!,#VENTPIPEAPPLICATIONSCOMPLY
with any additional requirements in the vent
SYSTEMMANUFACTURERSINSTRUCTIONS
Provide
A!,#STARTERPIECEFROMTHE!,#
MANUFACTURERTOTHE
transition at the boiler
VENTCONNECTION!IRPIPEMUSTBE06#OR
CPVC. Provide a 3” PVC transition at the
BOILERAIR CONNECTIONIFUSING v AIR PIPE
Provide transition pieces to PVC at the vent
and air pipe termination connections.
Wall penetration thickness between 2” to
24”.
$ETERMINETERMINATIONLOCATION
1. The concentric termination kit must be installed as
shown in Figure 29, page 26.
2. The termination must comply with clearances and
limitations shown in
Figure 22, page 21
.
3. Locate the termination so it is not likely to be damaged
BYFOREIGNOBJECTSSUCHASSTONESORBALLSORSUBJECT
TOBUILDUPOFLEAVESORSEDIMENT
-ULTIPLEVENTAIRTERMINATIONS
1. When terminating multiple boilers, install each con-
centric termination as described in this manual.
!LLVENTPIPESANDAIRINLETSMUSTTERMINATE
ATTHE SAME HEIGHT TOAVOIDPOSSIBILITY OF
severe personal injury, death or substantial
property damage.
2. Place wall penetrations to obtain minimum clearance
as shown in Figure 28, page 26FOR53INSTALLATIONS
3. 4HEAIRINLETOFA&REE3TYLE®BOILERISPARTOFADIRECT
VENTCONNECTION)TISNOTCLASSIlEDASAFORCEDAIRIN-
TAKEWITHREGARDTOSPACINGFROMADJACENTBOILERVENTS
&IGURE ).34!,,!4)/.3%15%.#%#ONCENTRICHORIZONTAL
3TEP 2EADANDFOLLOWALLINSTRUCTIONSINTHISMANUAL$/./4PROCEED
WITH VENTAIR INSTALLATION UNTIL YOU HAVE READ PAGE 
THROUGHPAGE
3EENOTICESATLEFT
3TEP )NSTALLTHEBOILERINALOCATIONTHATALLOWSPROPERROUTINGOFALLVENT
and air piping to the selected sidewall location.
3TEP -AKESURETHESELECTEDSIDEWALLTERMINATIONLOCATIONCOMPLIESWITH
Figure 22, page 21-ULTIPLEBOILERCONCENTRICTERMINATIONSMUST
also comply with
Figure 28, page 26
.)
3TEP Use only the vent materials listed in Figure 21, page 19. Provide pipe
adapters where required.
3TEP Vent piping and air piping lengths must not exceed the values shown
in Figure 20, page 18.
3TEP 4HECONCENTRICTERMINATIONMUSTBEASSEMBLEDANDINSTALLEDBEFORE
PIPINGFROMTHEBOILERTOTHETERMINATION
3TEP Prepare the sidewall penetration — assemble the concentric ter-
mination kit and secure the cover plates as instructed in this sec-
tion. Provide the supports indicated and mount the termination
assembly. See “Install termination — concentric pipes” on page 26.
3EENOTICESATLEFT
3TEP Install vent and air piping between the boiler and the concentric
vent/air termination. Slope horizontal piping downward toward the
BOILERATLEASTINCHPERFOOT3EE page 32FORGENERALGUIDELINES
3TEP )NSTALLPIPESUPPORTSEVERYFEETONBOTHTHEHORIZONTALANDVERTICAL
runs.
3EENOTICESATLEFT
3TEP )NSTALLAHANGERSUPPORTWITHININCHESOFANYUPTURNINTHEPIPING
3EENOTICESATLEFT
53%37%%0%,"/73&/2!,,6%.4!.$!)2
0)0).'$/./4USESHORTRADIUSELBOWSFORVENTOR
AIRPIPING"OILERPERFORMANCECOULDBEAFFECTED

Table of Contents

Other manuals for Freestyle 80

Related product manuals