EasyManua.ls Logo

Freestyle 80 - DIRECT VENT - Vertical Concentric

Freestyle 80
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 32 ).34!,,!4)/.3%15%.#%#ONCENTRICVERTICAL
Part number 550-142-850/0716
29
FreeStyle
®
WALL MOUNT GAS-FIRED WATER BOILERBoiler Manual
Allowable vent/air pipe materials &
lengths
1. The concentric termination kit must be purchased
separately.
Use only the vent materials and kits listed in
Figure 21, page 190ROVIDEPIPEADAPTERSIF
specified.
2. Locate the termination such that the total air piping and
VENTPIPINGFROMTHEBOILERTOTHETERMINATIONWILLNOT
exceed the maximum length given in Figure 20, page 18.
3. This termination requires a 45-degree elbow that is not
supplied with the termination kit. The maximum vent/
AIRPIPELENGTHSINCLUDEALLOWANCEFORTHISELBOW
For polypropylene applications, comply
with any additional requirements in the vent
SYSTEMMANUFACTURERSINSTRUCTIONS(Do Not
use 3” PVC transition pieces at the boiler vent
and air connections)ANDATTHETERMINATIONIF
using a 3” PVC concentric vent kit. Install a
locking collar at every joint.
&OR!,#VENTPIPEAPPLICATIONSCOMPLY
with any additional requirements in the vent
SYSTEMMANUFACTURERSINSTRUCTIONSProvide
A!,#STARTERPIECEFROMTHE!,#
MANUFACTURERTOTHE transition at the boiler
VENTCONNECTION!IR PIPE MUST BE06#OR
CPVC. Provide a 3” PVC transition at the
BOILERAIR CONNECTIONIFUSING v AIR PIPE
Provide transition pieces to PVC at the vent
and air pipe termination connections.
$ETERMINETERMINATIONLOCATION
,OCATETHE CONCENTRICVENTAIRTERMINATIONUSINGTHE FOL-
lowing guidelines:
1. The concentric vent/air assembly must terminate as
shown in Figure 34, page 30.
2. The termination must comply with the clearances and
limitations shown in Figure 21, page 22.
3. Locate the termination so it is not likely to be damaged
BYFOREIGNOBJECTSSUCHASSTONESORBALLSORSUBJECTTO
BUILDUPOFLEAVESORSEDIMENT
-ULTIPLEVENTAIRTERMINATIONS
1. When terminating multiple boilers, install the con-
centric vent/air termination assemblies as described in
this manual.
!LLVENTOUTLETSMUSTTERMINATEATTHESAME
HEIGHTTOAVOIDPOSSIBILITYOFSEVEREPERSONAL
injury, death or substantial property damage.
2. 0LACEROOFPENETRATIONSTOOBTAINMINIMUMCLEAR-
ANCEOFINCHESBETWEENTHEEDGESOFADJACENT
VENTPIPESOFOTHERBOILERSFOR53INSTALLATIONSSEE
Figure 33, page 30).
3. 4HEAIRINLETOFAFreeStyle®BOILERISPARTOFADIRECT
VENTCONNECTION)TISNOTCLASSIlEDASAFORCEDAIRIN-
TAKEWITHREGARDTOSPACINGFROMADJACENTBOILERVENTS
13 DIRECT VENT — 6ERTICALCONCENTRIC
3TEP 2EADANDFOLLOWALL INSTRUCTIONS IN THIS MANUAL$/ ./4
PROCEEDWITHVENTAIRINSTALLATIONUNTILYOUHAVEREAD
PAGETHROUGHPAGE
See notices
ATLEFT
3TEP )NSTALLTHEBOILERINALOCATIONTHATALLOWSPROPERROUTINGOFALL
vent and air piping to the selected sidewall location.
3TEP -AKESURETHESELECTEDVERTICALTERMINATIONLOCATIONCOMPLIES
WITH&IGUREPAGE-ULTIPLEBOILERCONCENTRICTERMINATIONS
must also comply with Figure 33, page 30.)
3TEP Use only the vent materials listed in Figure 21, page 19. Provide
pipe adapters where required.
3TEP Vent piping and air piping lengths must not exceed the values
shown in Figure 20, page 18.
3TEP The concentric termination must be assembled and installed
BEFOREPIPINGFROMTHEBOILERTOTHETERMINATION
3TEP Prepare the vertical penetration(s) — assemble the concentric
termination kit and secure the penetration components as
instructed in this section. Provide the supports indicated and
MOUNTTHETERMINATIONASSEMBLY3EEh0REPAREROOFPENETRATIONSv
on page 30ANDh-OUNTCONCENTRICTERMINATIONvON page 30.
3EENOTICESATLEFT
3TEP Install vent and air piping between the boiler and the concentric
vent/air termination. Slope horizontal piping downward toward
THEBOILER AT LEAST  INCHPER FOOT3EE page 32 FOR GENERAL
guidelines.
3TEP )NSTALLPIPESUPPORTS EVERY  FEET ONBOTHTHEHORIZONTALAND
vertical runs.
3EENOTICESATLEFT
3TEP )NSTALLAHANGERSUPPORTWITHININCHESOFANYUPTURNINTHE
piping.
3EENOTICESATLEFT
53%37%%0%,"/73 &/2 !,,6%.4!.$
!)2 0)0).' — DO NOT use short radius elbows
FORVENTOR AIRPIPING"OILER PERFORMANCECOULDBE
AFFECTED

Table of Contents

Other manuals for Freestyle 80

Related product manuals