NOTE!
A residual current circuit breaker for the AC connecting cable may be required de-
pending on local regulations, the grid operator, and other conditions.
A type A residual current circuit breaker with a trip current of at least 100 mA is generally
sufficient in this case. However, false alarms can be triggered for the residual current circuit
breaker type A in individual cases and depending on local conditions. For this reason, Fro-
nius recommends that you use a residual current circuit breaker suitable for frequency con-
verters.
Additional exter-
nal AC and/or DC
disconnect
Depending on the installation, an additional external AC and/or DC disconnect may be re-
quired if the inverter is installed in a location not easily accessible to utility or fire personnel.
Contact your local authorities for additional information.

Table of Contents

Other manuals for Fronius SYMO Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius SYMO Series and is the answer not in the manual?

Fronius SYMO Series Specifications

General IconGeneral
MPPT Number2
Frequency Range50 / 60 Hz
Operating Temperature Range-25°C to +60°C
CommunicationWiFi, Ethernet, RS485
AC Nominal Voltage3 x 230 V / 400 V
Output Voltage3 x 230 V / 400 V
Warranty5 years