CAUTION!
Danger due to heat generation on the device!
The build-up of heat can lead to lasting damage and even fire.
▶
Never cover the device during charging.
▶
Unwind the cable completely from a cable drum.
▶
Observe the correct installation position.
Never pull the plug out of the plug connection by the cable!
Observe the specifications of the grid operator regarding 1‑phase charging and the
asymmetrical network load that may result.
The device has a built-in residual current protection module with residual current detec-
tion (30 mA AC and 6 mA DC). This means that no upstream type B RCD is required. A
separate type A RCD and an automatic circuit breaker must be connected upstream for
each Wattpilot.
The device may only be operated at the following connections:
- CEE red 32 A, 3-phase, 400 V (Wattpilot Go 22 J)
- CEE red 16 A, 3-phase, 400 V (Wattpilot Go 11 J)
- With original adapters:
• CEE red 16 A, 3-phase, 400 V (Wattpilot Go 22 J)
• CEE red 32 A, 3-phase, 400 V (Wattpilot Go 11 J)
• CEE blue 16 A, 1-phase, 230 V
• Earthed plug 16 A, 1-phase, 230 V
In case of defective adapters or defective CEE plugs, send the device in for repair.
13