5-40
10% ED models
Braking resistor
Continuous braking
(100% braking torque)
Intermittent braking
(Period: Less than 100 s)
Power
supply
voltage
Inverter type
Type Qty.
Resistance
(:)
Discharging
capacity
(kWs)
Braking
time
(s)
Allowable
average loss
(kW)
Duty
(%ED)
FRNF12E1ع-2U
1000 100
FRNF25E1ع-2U
500 75
FRNF50E1ع-2U
250 37
FRN001E1ع-2U
DB0.75-2C 100 50
133
0.075
20
FRN002E1ع-2U
73 14
FRN003E1ع-2U
DB2.2-2C 40 55
50
0.110
FRN005E1ع-2U
DB3.7-2C 33 140 75 0.185
FRN007E1ع-2U
DB5.5-2C 20 55 20 0.275
FRN010E1ع-2U
DB7.5-2C 15 37 0.375
FRN015E1ع-2U
DB11-2C 10 55 0.55
Three-
phase
230 V
FRN020E1ع-2U
DB15-2C 8.6 75
10
0.75
10
FRNF50E1ع-4U
250 37
FRN001E1ع-4U
DB0.75-4C 200 50
133
0.075
20
FRN002E1ع-4U
73 14
FRN003E1ع-4U
DB2.2-4C 160 55
50
0.110
FRN005E1ع-4U
DB3.7-4C 130 140 75 0.185
FRN007E1ع-4U
DB5.5-4C 80 55 20 0.275
FRN010E1ع-4U
DB7.5-4C 60 38 0.375
FRN015E1ع-4U
DB11-4C 40 55 0.55
Three-
phase
460 V
FRN020E1ع-4U
DB15-4C 34.4 75
10
0.75
10
FRNF12E1ع-7U
1000 100
FRNF25E1ع-7U
500 75
FRNF50E1ع-7U
250 37
FRN001E1ع-7U
DB0.75-2C 100 50
133
0.075
20
FRN002E1ع-7U
73 14
Single-
phase
230 V
FRN003E1ع-7U
DB2.2-2C
1
40 55
50
0.110
10
Note 1: A box () in the above table replaces S or E depending on the enclosure.
E01 to E05,
E98, E99
Terminal [X1] to [X5] Function
Terminal [FWD] and [REV] Function
Function codes E01 to E05, E98 and E99 allow you to assign commands to terminals [X1] to
[X5], [FWD], and [REV] which are general-purpose, programmable, digital input terminals.
These function codes may also switch the logic system between normal and negative to
define how the inverter logic interprets either ON or OFF status of each terminal. The default
setting is normal logic system "Active ON." So, explanations that follow are given in normal
logic system "Active ON."
In the case of digital input, you can assign commands to the switching means for the run
command and its operation and the reference frequency (e.g., SS1, SS2, SS4, SS8, Hz2/Hz1,
Hz/PID, IVS, and LE). Be aware that switching any of such signals may cause a sudden start
(running) or an abrupt change in speed.
An accident or physical injury may result.