Fuji Electric Model: PXR4 - 2 nd Block Parameters

Fuji Electric Model: PXR4
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
Standby
AL2AL1C1 C2 AL3
SEL
PXR-4
SV
PV
Control output status
Alarm status
PV value
indication
SV value
indication
When the set value (SV) is displayed at the lower line, the SV lamp is lit.
AL2AL1C1 C2 AL3
SEL
PXR-4
SV
PV
Operation/Standby mode
SV value
indication
flickers.
SEL SEL
Operation
Parameter
Proportional band
Description of contents
Default
setting
Remarks
P
I
D
TC
TC2
CooL
db
P-SU
P-dP
ALM1
ALM2
HYS
Hysteresis for ON/OFF contorol
Cycle time (control output 2)
Deadband/overlap
Proportional band
coefficient on cooling side
Input type code
Lower limit of input range
As ordered
As ordered
P-n2
P-SL
As ordered
As ordered
0/5
0/9
5.0
Derivative action time
60.0
Integral time (reset)
240
Cycle time (control output 1)
Setting types of alarm action (Setting range: 0 to 34)
Setting of decimal point
position
PVOF
0
PV offset
Type of alarm 1
Upper limit of input range
Type of alarm 2
1
30/2 Note 2
30
1.0
0.0
PTn
1
Selects the ramp/soak execute type.
1: Executes 1st to 4th segment.
2. Executes 5th to 8th segment.
3. Executes 1st to 8th segment.
Ramp/soak execute type
SV-1
to
SV-8
0%FS
Sets the target SV for each ramp segment.
(Setting range: 0 to 100%FS)
Ramp target SV-1 to SV-8
TM1r
to
TM8r
0.00
Sets the time for each ramp segment.
(Setting range: 0 to 99 hours and 59 minutes)
1st ramp segment time to
8th ramp segment time
TM1S
to
TM8S
0.00
Sets the time for each soak segment.
(Setting range: 0 to 99 hours and 59 minutes)
1st soak segment time to
8th soak segmentl time
STAT
-
Ramp/soak status
Shift the display of process value (PV).
(Setting range: -10 to 10%FS)
Displays the current Ramp/Soak status.
No setting can be made.
Setting range: 0.0 to 999.9%
ON/OFF control when "P" = 0
Setting range: 0 to 3200 sec.
No integral action when "I" = 0
Setting range: 0.0 to 999.9 sec.
No derivative action when "d" = 0
Sets cycle time of control output 1.
(Setting range: 1 to 150 sec)
Setting range: 0 to 50% FS
Sets cycle time of control output 2.
(Setting range: 1 to 150 sec)
Sets the proportional band coefficient on the cooling side.
(Setting range : 0.0 to 100.0)
ON/OFF control when "Cool" = 0
Shifts the output value on the cooling side.
(Setting range: -50.0 to 50.0%)
Lower limit of input range
(Setting range: -1999 to 9999)
Upper limit of input range
(Setting range: -1999 to 9999)
Type of input Table 1
(Page 4)
Table 2
(Page 4)
Table 2
Table 2
(Page 4)
Table 3
(Page 4)
Table 3
(Page 4)
Select a decimal point position of display.
(Setting range: 0 to 2)
. .
"1"
0 : No decimal point
"2"
CTrL
PID
Type of control algorithm.
(Setting range: PID, FUZZY, SELF)
Control algorithm
P-dF
Time constant of input filter
5.0
Time constant (Setting range: 0.0 to 900.0 sec.)
2nd block parameter
Parameter
display symbol
Note 2
Table 2
(Page 4)
Press for about 3 sec. Press for about 2 sec.