– 14 –
Standby
AL2AL1C1 C2 AL3
SEL
PXR-4
SV
PV
Control output status
Alarm status
PV value
indication
SV value
indication
When the set value (SV) is displayed at the lower line, the SV lamp is lit.
AL2AL1C1 C2 AL3
SEL
PXR-4
SV
PV
Operation/Standby mode
SV value
indication
flickers.
SEL SEL
Operation
Parameter
Control action
Description of contents
Default
setting
Remarks
P-n1
A1hY
A2hY
dLY2
A1oP
A2oP
dLY1 ON delay time of
alarm 1
ON delay time of
alarm 2
Additional function
of alarm 2
Additional function
of alarm 1
Lower limit of SV
(Setting range: 0 to 100%FS)
Lower limit of SV
Upper limit of SV
(Setting range: 0 to 100%FS)
Upper limit of SV
0%FS
100%FS
SV-L
SV-H
0 Table 4
(Page 4)
6-7
(Page 3)
6-6
(Page 3)
Hysteresis for
alarm 1
Sets ON-OFF hysteresis for alarm output.
(Setting range: 0 to 50%FS)
1
Hysteresis for
alarm 2
ON delay time setting for alarm output
(Setting range: 0 to 9999 sec)
Additional function of alarm output
(Setting range: 000 to 111)
Alarm latch (1:use, 0:not use)
Alarm of error status (1:use 0:not use)
De-energized (1:use 0:not use), Note 3.
0
1
0
000
000
dl-1
CT
-
CT (Current Transformer) input valueCT input value
0(OFF)
Selects digital input 1 (DI1) function
(Setting range: 0 to 12)
DI1
function
STno
1
Communication station No. (Setting range: 0 to 255)Station No.
CoM
0
Parity setting
Parity setting. Baud rate is fixed at 9600 bps.
(Setting range: 0 to 2)
PYP
34
Code for PYP input
type
Input type code used when communicating with PYP.
See the OPERATION MANUAL
(Initial value: K: 0 to 400 C)
dSP1
to
dSP13
Parameter mask Specifying parameter mask
Selects the control action.
Hb
0.0
Sets current value to detect the heater disconnection
(Setting range: 1.0 to 50.0A, 0: OFF)
HB alarm set value
Parameter
display symbol
3rd block parameter
Note 3) De-energized: Contact opens when the alarm "ON".
Press for about 5 sec. Press for about 2 sec.