– 28 –
Input typeGroup
I
· Pt100 (IEC)
RTD
· J
· K
· R
· B
· S
· T
· E
· N
· PL-II
1
2
3
4
5
6
7
8
12
13
Thermocouple
Code
Input type
Group
II 1 to 5VDC,
4 to 20mA DC
16
Code
Can be modified by
changing "P-n2"
Modification
not possible
· In case of 4 to 20mA DC input, mount a 250Ω
resistor enclosed in the package box.
TC RTD
(within Group I)*
TC/RTD
1 to 5 VDC
4 to 20 mA DC
(Group I)* (Group II)*
(*) Outputs when Error Indication Group I.
Please refer to 8 (Error indications).
This is effective even in Standby mode.
Lower limit:OFF or 4mA or less
Upper limit:ON or 20mA or more
[Caution for dual output] (option)
(1) Parameter “I” and “D” can not be set
separately.
(2) In case “P”=0 (ON/OFF control) for heating
side, cooling side becomes ON/OFF
control automatically.
(3) In case “Cool” =0.0, cooling side becomes
ON/OFF control. And hysteresis is fixed at
0.5%FS.
Table 2
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Single
(Control output 1)
Dual
Control output
1 and 2.
Heating/Cooling
Output 1
Reverse action
Direct action
Reverse action
Direct action
Reverse action
Direct action
Output 2
---
Direct action
Reverse action
Output 1
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Output 2
---
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Lower limit
Upper limit
Control output action
Output at Burn-out*
Code
Output
Parameter :
Control output action code
Table 1
Input type code
Parameter :