– 21 –
1. Function
Changes the set value (SV) as the time elapses according to a predetermined program pattern, as shown
below.
Either 4 ramp/soak x 2 patterns or 8 ramp/soak x 1 pattern can be programmed. The first ramp starts from
the process value (PV) just before the programming is executed.
2. Setting
· Select the program pattern (PTn) and set the rUn at
“ProG” parameter.
· Ramp/soak pattern can not be changed while ramp/soak program is running.
Note:
· The ramp/soak program is canceled if the controller becomes to standby mode.
Then, if the controller becames to opration mode, the program doesn’t run again.
SV-1
SV-2
SV-3
SV-4
SV-5
SV-6
SV-7
SV-8
Time
TM1r
PV
TM1s TM4rTM4s TM5rTM5s TM8rTM8s
1st 4 ramp/soak 2nd 4 ramp/soak
8 steps
PTn
1
2
3
Pattern
1
2
1 + 2
Ramp/Soak
4
4
8
and/orand/or
6-5 Ramp/soak function [option]