2. Installation
Installing in a Rack
FUJITSU Storage ETERNUS AF, ETERNUS DX Configuration Guide (Power Synchronized Unit)
Copyright 2019 FUJITSU LIMITED P3AM-8012-14ENZ0
40
4 Attach the shelf plate to the AC sensor unit.
Use two M4 cross recessed head screws with captive washer to attach the shelf plate to the AC sensor unit.
5 Attach the shelf plate to the rack.
Use four M6 cross recessed head screws with captive washer to fasten the shelf plate in the rack.
Up to two AC sensor units can be attached to the same shelf plate. Attach the first AC sensor unit on
the right side when facing the shelf plate as shown in the figure above.
M4 cross recessed head screws with captive washer
Shelf plate
(Rear rack pillars)
M6 cross recessed head screws
with captive washer
M6 cross recessed head screws
with captive washer