2. SOFTWARE CONFIGURATION
2-9
2.4 Analog Signal
Analog signals are input via Sensor Adapter MC-3010A or the Interface Unit IF-8530.
The channel number depends on connected equipment. See the table below.
Channels are assigned according absence or presence of junction box(es). The num-
ber of junction boxes is set on [System] tab.
Receivable signal: -10 to +10 V or 4 to 20mA
Set the signal level of each channel accordingly.
How to set the analog channels
1. Click the [Analog] tab.
2. Select a channel from the [Information] window. Set detailed information of the
selected channel in the [Setting] window.
Note: In the default setting, there is no preset data when the [Select Equipment]
button is clicked. In the case that the setup was completed on another ship and
saved using [Reflect Equipment], import the data by clicking [Select Equipment]
and choosing the saved data.
3. Calibrate the Analog signal as
follows:
1) Click the [Calibration] button in
the [Setting] window.
2) Enter the voltage (or current)
value for [Calibration Point 1],
and the corresponding
engineering value in the left
and right fields.
3) Enter values for [Calibration
Point 2].
JB (Yes/No) JB CH Sensor Adapter 1 CH Sensor Adapter 2 CH
Yes CH1 - CH16 CH17 - CH31 CH32 - CH46
No - CH1 - CH15 CH16 - CH30