RC1xx LED Lighting Controllers - User Manual
31
Numeric parameters are separated by a comma (,). Time periods are
specied in milliseconds by default, but you can add ‘s’, ‘ms’, or ‘us’ to the
parameter to specify seconds, milliseconds, or microseconds. Current is
specied in amps by default, but you can add ‘A’ or ‘mA’ to the parameter
to specify amps or milliamps.
Note: All parameters are specied in the ‘USA/UK’ format, where a half is
written as ‘0.5’ and not ‘0,5’. Examples of acceptable parameters are shown
below:
0.1 0.1 milliseconds
200us 200 microseconds
0.1s 0.1 seconds
100mA 100 milliamps
2.45A 2.45 Amps
2.3 2300 milliamps, 2.3 Amps
10.3.3 General commands
Any changes you make using Ethernet commands are not saved
permanently until you send the AW command.
ReporttheRC120rmwareversion
This command returns the rmware version running on the RC120.
For example, typing:
VR returns
RC120 (HW101) V001
Save the settings to memory
AW
This command saves the settings to non-volatile memory. If you
power cycle the RC120 before sending the AW command, all changes
are lost and the unit returns to the values set before the last AW
command.
Settheoptionags
This command sets the ags for error detection, trigger sense, and
SafeSense:
RE1,m