EasyManua.ls Logo

GE Multilin 345 - Winding breakers

GE Multilin 345
254 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 6: SETPOINTS S2 SYSTEM SETUP
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–35
are the phase restraint currents.
Per the example, the per-phase differential and restraint currents would be as follows:
Winding breakers
The status of the Winding 1 breaker is monitored by the 345 relay using the status of either
one or two contact inputs, 52a (CI#1) and 52b (CI#2), wired to the Winding 1 breaker
auxiliary contacts 52a and 52b, and the status of the Winding 2 breaker 52a (CI#3) and 52b
(CI#4) wired to Winding 2 breaker aux contacts 52a and 52b respectively (see below).
The following path is available using the keypad. For instructions on how to use the
keypad, please refer to Chapter 3 - Working with the Keypad.
PATH:
SETPOINTS > S2 SYSTEM SETUP > WNDG 1 BREAKER
52a CONTACT
Range: Disabled, Contact Input 1
Default: Disabled
Select Contact Input 1 [52a (CI#1)] if connected to breaker auxiliary contact 52a.
52b CONTACT
Range: Disabled, Contact Input 2
Default: Disabled
Select Contact Input 2 [52b (CI#2)] if connected to breaker auxiliary contact 52b.
BKR CONNECTED
Range: Contact Input 5 to 10, Disabled
Default: Disabled
Select a contact input to show whether the breaker is connected (Racked-in, or
disconnect switches switched-on), or disconnected (racked-out, or disconnect switches
switched-off) to the system.
PATH:
SETPOINTS > S2 SYSTEM SETUP > WNDG 2 BREAKER
52a CONTACT
Range: Disabled, Contact Input 3
Default: Disabled
Select Contact Input 3 [52a (CI#3)] if connected to Winding 2 breaker auxiliary contact
52a.
52b CONTACT
Range: Disabled, Contact Input 4
Default: Disabled
Select Contact Input 4 [52b (CI#4)] if connected to Winding 2 breaker auxiliary contact
52b.

Table of Contents

Related product manuals