18.6 Full Scale Options 
  Caution 
If you change full scale options, 
recalibrate both channels and 
replace the meter scale on the 
front panel. 
 
CHANNEL A JUMPERS  CHANNEL B JUMPERS MONITOR 
FULL SCALE OPTIONS 
INSTALL REMOVE INSTALL REMOVE 
0 to 2 g pk 
  or 
0 to 20 m/s
2
 pk 
W4C 
W18D 
W4A,B,D 
W6C 
W2B 
W5D 
W2A,C,D 
W3D 
0 to 5 g pk 
  or 
0 to 50 m/s
2
 pk 
W4A,C 
W6C 
W4B,D 
W18D 
W2B,D 
W3D 
W2A,C 
W5D 
0 to 10 g pk 
  or 
0 to 100 m/s
2
 pk 
W4C 
W6C 
W4A,B,D 
W18D 
W2B 
W3D 
W2A,C,D 
W5D 
0 to 20 g pk 
  or 
0 to 200 m/s
2
 pk 
W4A 
W6C 
W4B,C,D 
W18D 
W2D 
W3D 
W2A,B,C 
W5D 
0 to 1 in/s pk 
  or 
0 to 25 mm/s pk 
W4A,C 
W4B,D 
W6C 
W18D 
W2B,D 
 
W2A,C 
W3D 
W5D 
0 to 2 in/s pk 
  or 
0 to 50 mm/s pk 
W4C 
W4A,B,D 
W6C 
W18D 
W2B 
 
W2A,C,D 
W3D 
W5D 
0 to 100 mm/s pk  W4A 
W4B,C,D 
W6C 
W18D 
W2D 
 
W2A,B,C 
W3D 
W5D