EasyManua.ls Logo

GE F650 - Page 186

GE F650
801 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GEK-106310AB F650 Digital Bay Controller 5-39
5 SETTINGS 5.4 PROTECTION ELEMENTS
5
5.4.2.3 IAC CURVES
This family of curves follows the time response of the General Electric IAC electromechanical relays. The following
formulas define these curves:
Where:
t = Operation time in seconds
Dial = multiplier setting
I = Input current
Itap = Current pickup value
A, B, C, D, E = predefined constants
T
RESET
= reset time in seconds
t
r
= characteristic constant.
Table 5–34: CONSTANTS FOR IAC CURVES
IAC CURVE SHAPE NAME A B C D E TR
IAC Extremely Inverse IAC Ext Inv 0.0040 0.6379 0.6200 1.7872 0.2461 6.008
IAC Very Inverse IAC Very Inv 0.0900 0.7955 0.1000 -1.2885 7.9586 4.678
IAC Inverse IAC Mod Inv 0.2078 0.8630 0.8000 -0.4180 0.1947 0.990