5-174 F650 Digital Bay Controller GEK-106310AB
5.13 IEC 60870-5-103 PROTOCOL CONFIGURATION 5 SETTINGS
5
Pressing the "Add" button the configured data will be added to the Measurands List. The processes of removing, updating
and saving are done in the same way as for digital states.
Figure 5–69: MEASURANDS CONFIGURATION FOR IEC 60870-5-103 PROTOCOL
Commands:
All the configurable commands and virtual inputs self-reset will be available in order to be mapped using the EnerVista 650
Setup program. It would be possible to choose the desired command for the ON state and the same or different command
for the OFF state.
The customer will be able to select the Information Number <1..255> and the Function Type <0..255>, but the Identification
Type 20 (General Commands) is fixed and it will be used to send a command to the slave station.
Pressing the "Add" button the configured data will be added to the Operations List. The processes of removing, updating
and saving are done in the same way as for digital states and for measurands.