GEK-106310AB F650 Digital Bay Controller 7-19
7 IEC 61850 PROTOCOL 7.2 IEC 61850 PROFILE FOR F650
7
2.3.3 MMS parameter Conformance Building Block (CBB)
2.3.4 GetNameList conformance statement
MMS parameter CBB
Client-CR Server-CR
realized Value/range realized Value/range
STR1
Y
STR2
Y
VNAM
Y
VALT
Y
VADR
N
VSCA
N
TPY
N
VLIS
Y
REAL
N
CEI
N
NEST
Y7
ACO
N
SEM
N
CSR
N
CSNC
N
CSPLC
N
CSPI
N
GetNameList
Client-CR Server-CR
realized Value/range realized Value/range
Request
ObjectClass Y
ObjectScope
Y
DomainName
Y
ContinueAfter
Y
Response+
List Of Identifier Y
MoreFollows
Y
Response–
Error Type Y
NOTE Object class ‘vmd' (formerly VMDSpecific in MMS V1.0) shall not appear. If a request contains this ObjectClass, an MMS
Reject shall be issued.