EasyManua.ls Logo

GE F650 - Page 393

GE F650
801 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-24 F650 Digital Bay Controller GEK-106310AB
7.2 IEC 61850 PROFILE FOR F650 7 IEC 61850 PROTOCOL
7
2 Logical Nodes and Extensions
Some of the following logical nodes have been extended with extra data. All extra data has been highligthed in the tables
and marked as “E” (Extended), these data contains “dataNs” attribute with the NameSpace “GE MICS for 650 family
rev1.3”.
Comments:
M: Data is mandatory in the IEC-61850-7-4.
O: Data is mandatory in the IEC-61850-7-4 and is used in the device.
E: Data is an extension to the IEC-61850-7-4.
2.1 System Logical Nodes. LN Group: L
2.1.1LPHD (Physical device information)
2.1.2 LLN0 (Logical node zero)
2.1.2.1 GsCB (GSSE control block class definition)
LPHD class
Attribute Name Attribute Type Explanation M/O/E Notes
LPHD Physical device information M
Data
Common Logical Node Information
PhyNam DPL Physical device name plate M
PhyHealth INS Physical device health M
Proxy SPS Indicates if this LN is a proxy M
LLN0 class
Attribute Name Attribute Type Explanation M/O/E Notes
LLN0 Logical node zero
Data
Common Logical Node Information
Mod INC Mode M Status-only
Beh INS Behaviour M
Health INS Health M
NamPlt LPL Name plate M
Loc SPS Local operation for complete logical device O
Optmh INS Operation time M
GsCB (ACSI class GSSE control block)
GsCB GsCB
GoCB (ACSI class GOOSE control block)
GoCB GoCB
SGCB (ACSI class Setting Group control block)
SGCB SGCB
GsCB class
Attribute Name Attribute Type FC Notes
GsEna BOOLEAN GS Enable (TRUE), disable (FALSE)
GsID VISIBLE STRING65 GS
DNALabels[1..n] VISIBLE STRING65 GS Labels of DNA bit pairs
UserSTLabels[1..n] VISIBLE STRING65 GS Label of ST bit pairs
LSentData [1..n] GSSEData GS Derived from GSSE message

Table of Contents