GEK-106310AB F650 Digital Bay Controller 2-13
2 PRODUCT DESCRIPTION 2.4 TECHNICAL SPECIFICATIONS
2
2.4.1.16   PHASE UNDERVOLTAGE (27P)
2.4.1.17   NEUTRAL OVERVOLTAGE (59NH/59NL)
2.4.1.18   NEGATIVE SEQUENCE OVERVOLTAGE (47)
Voltage Input Fundamental Phasor of phase-to-ground or phase-to-
phase voltages (selectable by setting)
Pickup level 3 to 300 in steps of 1 V
Dropout level 102% to 103% of the pickup level
Level accuracy
±1% of reading from 10 to 208 V
 at nominal frequency
Curve Shapes Fixed time or inverse curve
Reset type Instantaneous 
Curve Multiplier (Time Dial) 0.00 to 900.00 s. in steps of 0.01 s.
Timing accuracy ±3.5% of operate time or 50 ms. (whichever is greater)
Minimum Voltage Threshold 0 to 300 in steps of 1 V
Logic Any/Two/All phases logic selectable by setting
Supervised by Breaker Selectable by setting
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor of the neutral voltage 
Pickup level 3 to 300 in steps of 1 V
Dropout level 97% to 98% of the pickup level
Level accuracy
±1% of reading from 10 to 208 V
 at nominal frequency
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events Selectable by setting
Voltage Input Fundamental Phasor
Pickup level 3 to 300 in steps of 1 V
Dropout level 97% to 98% of the pickup level
Level accuracy
±1% of reading from 10 to 208 V
Trip delay 0.00 to 900.00 s. in steps of 0.01 s
Reset delay 0.00 to 900.00 s. in steps of 0.01 s
Timing accuracy ±3.5% of operate time or 50 ms. (whichever is greater)
Snapshot Events Selectable by setting