2-24 F650 Digital Bay Controller GEK-106310AB
2.4 TECHNICAL SPECIFICATIONS 2 PRODUCT DESCRIPTION
2
2.4.5.7 WAR-HOURS (POSITIVE AND NEGATIVE)
2.4.5.8 FREQUENCY
2.4.5.9 ANGLE
2.4.6 INPUTS
2.4.6.1 AC CURRENT INPUTS
Accuracy:
±2.0% of the reading
Range: -2147483 to +2147483 MVArh
Parameters: 3-phase only
Update rate: 100 ms
Accuracy: +/- 0.03Hz From 30 to 80 Hz
Accuracy: ±3º
CT Ratio: 1.0 to 6000.0 in steps of 0.1
Rated currents: Appropriate for 1 or 5 A. F650 has universal range for CT (valid for 1 or 5 A to
only one terminal).
Relay Burden: < 0.04 Ohm
Current Withstand Continuous at 20 A
1 second at 500 A for phases and ground
1 second at 50 A for sensitive ground