OPM_LPS_33E_60K_M12_2GB_V010.doc Operating Manual LP 33 Series 60-80-100-120 kVA / S2
5.7.2 Fuse ratings
If ELCB breakers are prescribed to protect the input connections, consider the high leakage current
towards the earth generated by the noise-suppressor capacitors.
If strongly prescribed, the ELCB breakers should be the largest type suitable for non-linear current and
for delayed operation.
Common input Rectifier & Bypass
Separate input Rectifier & Bypass
(optional)
Fig. 5.7.2-1 Common input Rectifier & Bypass
Fig. 5.7.2-2 Separate input Rectifier & Bypass (optional)
Fuses AgL or equivalent MTCB
for mains voltages 3x380/220V, 3x400/230V, 3x415/240V
UPS model
F1 F2 F3 F4 (external battery)
LP 33 Series 60 kVA
3 x 100 A 3 x 100 A 3 x 100 A 3 x 125 A
LP 33 Series 80 kVA
3 x 125 A 3 x 125 A 3 x 125 A 3 x 160 A
LP 33 Series 100 kVA
3 x 160 A 3 x 160 A 3 x 160 A 3 x 200 A
LP 33 Series 120 kVA
3 x 200 A 3 x 200 A 3 x 200 A 3 x 250 A