Modifications reserved Page 96/103
OPM_LPS_33E_60K_M12_2GB_V010.doc Operating Manual LP 33 Series 60-80-100-120 kVA / S2
10 OPTIONS
10.1 OPTIONS GENERAL VIEW
Mains Input
LPS33_060-080_S2_RPA s ystem_GE_01
LP 33 Series
1
LP 33 Series
2
LP 33 Series
3
LP 33 Series
4
RPA
Board
RPA
Board
RPA
Board
RPA
Board
F2F1 F3 F4
Inverter Total Off
g
Inverter Total Off
g
Inverter Total Off
g
Inverter Total Off
g
Load
RPA kit
Redundant Parallel Architecture
Allows to extend the unit to a Parallel System with 2, 3, or 4 units connected on the same bus,
which ensure the highest reliability rate and increase the power availability without prior
investments.
2
1
L
P
S
3
3
_
0
6
0
-
1
2
0
_
O
P
T
_
C
a
b
i
n
e
t
s
b
a
t
t
e
r
y
_
0
1
3
Battery Extension Packs
Extended run-time versions are equipped with additional batteries housed in the UPS itself, to
increase the back-up time of the UPS when the mains fails.
Additional battery cabinets
Depending on model the battery extensions can be housed in additional cabinets with the
same design of the UPS cabinet, delivered with the necessary protection and connection
material.
For extended run-time versions and additional cabinets see enclosed Data Sheets.
SGT4000_custom er interface_02
1234567891011
1615141312 222120191817
21
Customer Interface
The Customer Interface allows the client the exchange of information (monitoring and control)
with the following interfaces:
- Serial port RS232.
- 6 programmable output channels.
- 2 programmable input channels, of witch one for GEN-ON.
- EPO (Emergency Power Off).
Advanced SNMP Card
Simple Network Management Protocol
The Advanced SNMP Card is an Interface to the Ethernet Network, and provides UPS
information via the standard SNMP protocol.
The UPS can therefore be managed by a Network Management System (NMS) or by our
applications (for instance JUMP), which uses this information to determine the state of the UPS
in order to guarantee safe and orderly shutdown of the server, when needed.
GE Power Diagnostics
GE Power Diagnostics is an anytime, anywhere concept in UPS status monitoring and alarm
notication that has been successfully implemented in numerous of installations supporting
up to multi-hundred UPS.
Based on the leading Intelligent Remote Information System IRIS all GE UPS types as well as
3rd party UPS are supported.
Accessing the latest site information via Web and being alerted by Email, SMS or Fax, it
enables the user to make timely decisions in case of changing critical conditions.
With comprehensive data collection and analysis IRIS is not only a remote monitoring &
diagnostics (RM&D) system but, the core of the integrated service offering GE Power
Diagnostics.
GE Data Protection
GE Data Protection software can communicate with the UPS over RS-232, USB or SNMP to
receive status information and measurement values of the UPS.
In case of a critical condition (time on battery, remaining battery autonomy time or low
battery) for the load, the software starts a controlled shutdown.
An enhanced alarm management system provides the possibility to start applications, send
messages, and send e-mails for every upcoming or disappearing alarm.

Table of Contents