OPM_LPS_33E_60K_M12_2GB_V010.doc Operating Manual LP 33 Series 60-80-100-120 kVA / S2
LP Series S2 100kVA
UPS Model UPS series number
UPS nominal rating (kVA)
Battery level LED
All LED light indicate a battery autonomy of 100%.
LED A Fixed: indicates a battery autonomy between 6% and 25%.
Blinking: indicates a battery autonomy ≤5%.
LED A, B Indicate a battery autonomy between 26% and 50%.
LED A, B, C Indicate a battery autonomy between 51% and 99%.
Min: Battery autonomy time in minutes estimates with actual load.
Load level LED
All LED Off indicate a load status at ≤25%.
LED A Indicates a load level between 26% and 50%.
LED A, B Indicate a load level between 51% and 75%.
LED A, B, C Indicate a load level between 76% and 100%.
LED A, B, C, D Indicate a load level between 101% and 124%.
LED D blinking Indicates a load level ≥125%.
Fig. 7.1-2 LEDs on synoptic diagram
LEDs on synoptic diagram
LED 1 Mains rectifier OK
LED 2 Mains bypass OK
LED 3 Rectifier ON
LED 4 Discharging battery
LED 5 Booster ON
LED 6 Charge battery ON
LED 7 Inverter available
LED 8 Inverter ON
LED 9 Q1 closed
LED 10 Automatic bypass ON
LED 11 Manual Bypass Q2 ON
LED 12 Load on UPS
Examples of typical scenarios in the synoptic diagram:
Load supplied by inverter Load supplied by automatic bypass