OPM_LPS_33E_60K_M12_2GB_V010.doc Operating Manual LP 33 Series 60-80-100-120 kVA / S2
Example 5:
An equivalent set of parameters for Example 4 is.
Weekday
d1 - Saturday d2 - Sunday d3 - Monday d4 - Tuesday d5 - Wednesday d6 - Thursday d7 - Friday
ECO Mode START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
ECO Mode STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
ECO Mode START
ECO Mode STOP
The ECO Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 - Tuesday (as
indicated by the ECO Mode STOP time of weekday d4 - Tuesday).
The ECO Mode STOP time of weekday d3 - Monday has no effect as it is followed by the ECO Mode STOP
time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the ECO Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of weekday d5 -
Wednesday.
The ECO Mode START time of weekday d5 - Wednesday has no effect as it is preceded by the ECO Mode
START time of weekday d4 - Tuesday.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired ECO Mode operation, verify:
Date and Time (first page of parameter).
ECO mode screen how many hours of ECO Mode operation have been selected for
each day of the week.
NOTE !
The ECO Mode will become active only if the load is supplied from the inverter.