OPM_LPS_33E_60K_M12_2GB_V010.doc Operating Manual LP 33 Series 60-80-100-120 kVA / S2
STORAGE
Store the UPS in a dry location; storage temperature must be within -25°C to 55°C (-13°F to 131°F).
If the unit is stored for a period exceeding 3 months, the batteries must be recharged periodically
(time depending on storage temperature).
BATTERY
The battery-voltage is dangerous for person’s safety.
When replacing the battery, use the same number, voltage (V) and capacity (Ah).
Do not connect battery strings of different type in parallel.
Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
Never dispose of battery in a fire: they may explode.
Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
Avoid charging in a sealed container.
Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated
tools.
WARNING !
The UPS contains hazardous voltages.
Observe carefully the safety instructions to prevent risk of
electrical shock.
Parallel version secured with RPA
When included in the text, this symbol refers to operation
needed only for Parallel System.