GE Power Management
MM2 Motor Manager 2 6-33
6 COMMUNICATIONS 6.5 MEMORY MAP
6
ANALOG
INPUT
continued
44371 4370 1112 Analog High Override Delay 1-126 1 s F1* 5
44372 4371 1113 ...Reserved... ... ... ... ... ...
44373 4372 1114 ...Reserved... ... ... ... ... ...
44374 4373 1115 ...Reserved... ... ... ... ... ...
44375 4374 1116 ...Reserved... ... ... ... ... ...
44376 4375 1117 ...Reserved... ... ... ... ... ...
44377 4376 1118 ...Reserved... ... ... ... ... ...
44378 4377 1119 ...Reserved... ... ... ... ... ...
44379 4378 111A ...Reserved... ... ... ... ... ...
44380 4379 111B ...Reserved... ... ... ... ... ...
44381 4380 111C ...Reserved... ... ... ... ... ...
44382 4381 111D ...Reserved... ... ... ... ... ...
44383 4382 111E ...Reserved... ... ... ... ... ...
44384 4383 111F ...Reserved... ... ... ... ... ...
U / V
AUTO
RESTART
44385 4384 1120 Undervoltage Restart 0-1 1 --- F14 1 = ENABLE
44386 4385 1121 Immediate Restart Power Loss Time 100-520 20 ms F1* 200
44387 4386 1122 Delayed Restart Power Loss Time 1-101 1 0.1 x s F1*** 20 = 2.0 s
44388 4387 1123 Restart Time Delay 2-12000 2 0.1 x s F1 20 = 2.0 s
44389 4388 1124 ...Reserved... ... ... ... ... ...
↓↓↓ ↓ ↓ ↓ ↓↓ ↓
44392 4391 1127 ...Reserved... ... ... ... ... ...
AUX 1
RELAY
44393 4392 1128 AUX Relay 1 Function 0-33 1 --- F20 0=SERIAL
CNTL
44394 4393 1129 AUX Relay 1 Delay 0-125 1 s F1 5
44395 4394 112A AUX Relay 1 Motor Start Delay 0-125 1 s F1 5
44396 4395 112B AUX Relay 1 Motor Stop Delay 0-125 1 s F1 5
44397 4396 112C AUX Relay 1 Pre Delay 0-900 1 s F1 5
44398 4397 112D AUX Relay 1 Post Delay 0-126 1 s F1* 126 = OFF
44399 4398 112E AUX Relay 1 Operation 0-1 1 --- F12 0=non-failsafe
44400 4399 112F ...Reserved... ... ... ... ... ...
PLANT
CONDI-
TION
44401 4400 1130 Drive Greasing Interval
100-50100
100 hours F1* 65535 = OFF
44402 4401 1131 Contactor Inspection Interval 1-10001 1 x1000 Op F1* 65535 = OFF
44403 4402 1132 Maximum Drive Stopped Time
100-10100
100 hours F1* 65535 = OFF
44404 4403 1133 ...Reserved... ... ... ... ... ...
↓↓↓ ↓ ↓ ↓ ↓↓ ↓
Table 6–12: MODBUS MEMORY MAP (Sheet 14 of 21)
GROUP MOD-
ICON
REGISTER
ADDRESS DESCRIPTION REGISTE
R VALUE
RANGE
STEP
VALUE
UNITS
AND
SCALE
FOR-
MAT
FACTORY
DEFAULT
VALUE
(CONVERTED)
DEC HEX
Notes: * – Maximum setpoint value and 65535 represent OFF
** – 1/Phase Current Scale Factor x A
*** – 101 represents unlimited
† – Minimum setpoint value represents OFF
~* – 0.1 x A when Hi resolution mode is disabled; 0.01 x A when enabled