EasyManua.ls Logo

GE MOTOR MANAGER 2 - Mm2 Sequences

GE MOTOR MANAGER 2
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Power Management
MM2 Motor Manager 2 9-7
9 STARTER TYPES 9.3 TWO SPEED STARTER
9
9.3.2 MM2 SEQUENCES
START LOW SPEED sequence:
1. Start A command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Contactor A relay – the motor is now in low speed.
START DIRECTLY TO HIGH SPEED (motor stopped, HIGH SPEED START BLOCK not enabled)
sequence:
1. Start B command received by the MM2 (serial, switch input or faceplate).
2. Close and maintain Contactor B relay – the motor is now in high speed.
START DIRECTLY TO HIGH SPEED (motor stopped, HIGH SPEED START BLOCK enabled) sequence:
1. Start B command received by the MM2 (serial, switch input or faceplate).
2. No response to start B commands.
LOW TO HIGH SPEED TRANSITION sequence:
1. Start B command is received (serial, switch input or faceplate).
2. Open contactor A output relay.
3. Close and maintain Contactor B relay – the motor is now in high speed.
HIGH TO LOW SPEED TRANSITION sequence:
1. Start A command is received (serial, switch input or faceplate).
2. Open contactor B output relay.
3. Wait for the programmed transfer time.
4. Close and maintain contactor A.
STOP/TRIP sequence:
1. Stop command received by the MM2 or a trip occurs.
2. Open the currently closed contactor output relay.
There are many different configurations for the TWO SPEED starter type. Three of the more popular
ones are illustrated here: two-speed one winding constant or variable torque, two-speed one winding
constant horsepower, and two-speed two winding. See the two speed starter diagrams on the follow-
ing pages.
When the power to the MM2 is interrupted, all MM2 output relays de-energize, causing them to open
and stop the motor. The MM2 can only be wired for fail-safe operation.
If feedback is not received from the L or H contacts to the Contactor A or B Status N.O. input within
one second of closing Contactor A relay, an OPEN CONTROL CIRCUIT alarm will occur. This will
cause Contactor A and B output relays to open.
If feedback remains at the Contactor A or B Status N.O. input more than one second after opening
the Contactor A or B output relays, a WELDED CONTACTOR alarm will occur.

Table of Contents

Related product manuals