EasyManua.ls Logo

GE Multilin EPM 6000 - Page 74

GE Multilin EPM 6000
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5–4 EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 5: COMMUNICATIONS
0C2F - 0C30
Positive VARs, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M VARs
2
0C31 - 0C32
Negative Watts, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M watts
2
0C33 - 0C34
Negative VARs, 3-Ph,
Maximum Avg Demand
FLOAT 0 to +9999 M VARs
2
0C35 - 0C36
VAs, 3-Ph, Maximum Avg
Demand
FLOAT -9999 M to +9999 M VAs
2
0C37 - 0C38
Positive Power Factor, 3-
Ph, Maximum Avg
Demand
FLOAT -1.00 to +1.00 none
2
0C39 - 0C3A
Negative Power Factor, 3-
Ph, Maximum Avg
Demand
FLOAT -1.00 to +1.00 none
2
0C3B - 0C3C Frequency, Maximum FLOAT 0 to 65.00 Hz
2
Block Size:
34
THD Block
7, 13
read-only
0F9F - 0F9F Volts A-N, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA0 - 0FA0 Volts B-N, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA1 - 0FA1 Volts C-N, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA2 - 0FA2 Amps A, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA3 - 0FA3 Amps B, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA4 - 0FA4 Amps C, %THD UINT16 0 to 9999, or 65535 0.1%
1
0FA5 - 0FA5
Phase A Current 0th
harmonic magnitude
UINT16 0 to 65535 none
1
0FA6 - 0FA6
Phase A Current 1st
harmonic magnitude
UINT16 0 to 65535 none
1
0FA7 - 0FA7
Phase A Current 2nd
harmonic magnitude
UINT16 0 to 65535 none
1
0FA8 - 0FA8
Phase A Current 3rd
harmonic magnitude
UINT16 0 to 65535 none
1
0FA9 - 0FA9
Phase A Current 4th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAA - 0FAA
Phase A Current 5th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAB - 0FAB
Phase A Current 6th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAC - 0FAC
Phase A Current 7th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAD - 0FAD
Phase A Voltage 0th
harmonic magnitude
UINT16 0 to 65535 none
1
0FAE - 0FAE
Phase A Voltage 1st
harmonic magnitude
UINT16 0 to 65535 none
1
0FAF - 0FAF
Phase A Voltage 2nd
harmonic magnitude
UINT16 0 to 65535 none
1
0FB0 - 0FB0
Phase A Voltage 3rd
harmonic magnitude
UINT16 0 to 65535 none
1
0FB1 - 0FB8
Phase B Current
same as Phase A Current 0th to 7th harmonic magnitudes
8
0FB9 - 0FBC
Phase B Voltage
same as Phase A Voltage 0th to 3rd harmonic magnitudes
4
0FBD - 0FC4
Phase C Current
same as Phase A Current 0th to 7th harmonic magnitudes
8
0FC5 - 0FC8
Phase C Voltage
same as Phase A Voltage 0th to 3rd harmonic magnitudes
4
Block Size:
42
Phase Angle Block
14
read-only
1003 - 1003 Phase A Current SINT16 -1800 to +1800 0.1 degree
1
1004 - 1004 Phase B Current SINT16 -1800 to +1800 0.1 degree
1
1005 - 1005 Phase C Current SINT16 -1800 to +1800 0.1 degree
1
1006 - 1006 Angle, Volts A-B SINT16 -1800 to +1800 0.1 degree
1
1007 - 1007 Angle, Volts B-C SINT16 -1800 to +1800 0.1 degree
1
1008 - 1008 Angle, Volts C-A SINT16 -1800 to +1800 0.1 degree
1
Block Size:
6
HEX
ADDRESS
DESCRIPTION
1
FORMAT RANGE
6
UNITS OR
RESOLUTION
COMMENTS # REG

Table of Contents

Related product manuals