CHAPTER 5: COMMUNICATIONS
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE 5–5
Status Block
read-only
1387 - 1387 Meter Status UINT16 bit-mapped --exnpch ssssssss
exnpch = EEPROM block OK flags
(e=energy, x=max, n=min,
p=programmable settings,
c=calibration, h=header),
ssssssss = state (1=Run, 2=Limp,
10=Prog Set Update via buttons,
11=Prog Set Update via IrDA, 12=Prog
Set Update via COM2)
1
1388 - 1388
Limits Status
7
UINT16 bit-mapped 87654321 87654321
high byte is setpt 1, 0=in, 1=out
low byte is setpt 2, 0=in, 1=out
1
1389 - 138A Time Since Reset UINT32 0 to 4294967294 4 msec wraps around after max count
2
Block Size:
4
COMMANDS SECTION
4
Resets Block
9
write-only
4E1F - 4E1F Reset Max/Min Blocks UINT16
password
5
1
4E20 - 4E20
Reset Energy
Accumulators
UINT16
password
5
1
Block Size:
2
Meter Programming Block
read/conditional write
55EF - 55EF
Initiate Programmable
Settings Update
UINT16
password
5
meter enters PS update mode
1
55F0 - 55F0
Terminate Programmable
Settings Update
3
UINT16 any value
meter leaves PS update mode via
reset
1
55F1 - 55F1
Calculate Programmable
Settings Checksum
3
UINT16
meter calculates checksum on RAM
copy of PS block
1
55F2 - 55F2
Programmable Settings
Checksum
3
UINT16
read/write checksum register; PS
block saved in EEPROM on write
8
1
55F3 - 55F3
Write New Password
3
UINT16 0000 to 9999 write-only register; always reads zero
1
59D7 - 59D7
Initiate Meter Firmware
Reprogramming
UINT16
password
5
1
Block Size:
6
Other Commands Block
read/write
61A7 - 61A7 Force Meter Restart UINT16
password
5
causes a watchdog reset, always
reads 0
1
Block Size:
1
Encryption Block
read/write
658F - 659A
Perform a Secure
Operation
UINT16
encrypted command to read
password or change meter type
12
Block Size:
12
PROGRAMMABLE SETTINGS SECTION
Basic Setups Block
write only in PS update mode
752F - 752F
CT multiplier &
denominator
UINT16 bit-mapped
dddddddd
mmmmmmmm
high byte is denominator (1 or 5, read-
only),
low byte is multiplier (1, 10, or 100)
1
7530 - 7530 CT numerator UINT16 1 to 9999 none
1
7531 - 7531 PT numerator UINT16 1 to 9999 none
1
HEX
ADDRESS
DESCRIPTION
1
FORMAT RANGE
6
UNITS OR
RESOLUTION
COMMENTS # REG

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Multilin EPM 6000 and is the answer not in the manual?

GE Multilin EPM 6000 Specifications

General IconGeneral
BrandGE
ModelMultilin EPM 6000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals