EasyManua.ls Logo

GE Multilin PQM - Page 128

GE Multilin PQM
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5–6 PQM POWER QUALITY METER – INSTRUCTION MANUAL
A1 METERING CHAPTER 5: MONITORING
Iavg/Vavg: Displays the average of the three phase currents/voltages. This value is not
visible if the
VT WIRING setpoint is set to SINGLE PHASE DIRECT. L-N is displayed when VT
WIRING
is set to 4 WIRE WYE (3 VTs), 4 WIRE WYE DIRECT, 4 WIRE WYE (2 VTs), or 3 WIRE
DIRECT and L-L is displayed when
VT WIRING is set to 3 WIRE DELTA (2 VTs).
Vab, Vbc, Vca, VOLTAGE: Displays each line voltage corresponding to the A, B, and C
voltage inputs. The measured voltage is correct only if the
VT RATIO, VT NOMINAL
SECONDARY
, and VOLTAGE WIRING setpoints match the installed VTs. If the displayed
voltage does not match the actual voltage, check the setpoints and wiring.
AVERAGE LINE VOLTAGE: Displays the average of the three line voltages. This value is not
visible if the
VT WIRING setpoint is set to SINGLE PHASE DIRECT.
VOLTAGE UNBALANCE: Displays the percentage voltage unbalance. Voltage unbalance is
calculated as shown below. If the
VOLTAGE WIRING is configured for a WYE input, voltage
unbalance is calculated using phase quantities. If the
VT WIRING is configured as a DELTA
input, voltage unbalance is calculated using line voltages.
where:V
av
= average phase voltage = (V
an
+ V
bn
+ V
cn
) / 3 for WYE and 3 WIRE DIRECT
connections
= average line voltage (V
ab
+ V
bc
+ V
ca
) / 3 for 3 WIRE DELTA/2 VTs connection
V
m
= voltage in a phase (or line) with maximum deviation from V
av
,
Even though it is possible to achieve unbalance greater than 100% with the
above formula, the PQM will limit unbalance readings to 100%.
If the average voltage is below 10% of
VT RATIO × VT NOMINAL SECONDARY VOLTAGE
for 3 WIRE DELTA/2 VTs, 4 WIRE WYE/3 VTs, and 4 WIRE WYE/2 VTs connections, or below
10% of
VT RATIO × NOMINAL DIRECT INPUT VOLTAGE for 4 WIRE WYE/DIRECT and 3
WIRE DIRECT connections, the unbalance reading is forced to 0%. This is implemented to
avoid nuisance alarms when the system is lightly loaded. If the simulation voltages are
being used, the unbalance is never forced to 0%.
Van, Vbn, Vcn MINIMUM: Displays the minimum phase voltage magnitudes and the time
and date of their occurrence. This information is stored in non-volatile memory and is
retained during loss of control power. The
S1 PQM SETUP \ CLEAR DATA \ CLEAR MIN/
MAX VOLTAGE VALUES
setpoint clears these values.
Vab, Vbc, Vca MINIMUM: Displays the minimum line voltage magnitudes and the time and
date of their occurrence. This information is stored in non-volatile memory and is retained
during loss of control power. The
S1 PQM SETUP \ CLEAR DATA \ CLEAR MIN/MAX
VOLTAGE VALUES
setpoint clears these values.
V U/B MINIMUM: Displays minimum voltage unbalance and the time and date of its
measurement. This information is stored in non-volatile memory and is retained during
loss of control power. This value is cleared with the
S1 PQM SETUP \ CLEAR DATA \
CLEAR MIN/MAX VOLTAGE VALUES
setpoint.
V
m
V
av
V
av
------------------------
100%×
NOTE
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals