7–24 PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP CHAPTER 7: MODBUS COMMUNICATIONS
VOLTAGE
0280
0281
Voltage Van (High)
Voltage Van (Low)
--- --- V F3 N/A
0282
0283
Voltage Vbn (High)
Voltage Vbn (Low)
--- --- V F3 N/A
0284
0285
Voltage Vcn (High)
Voltage Vcn (Low)
--- --- V F3 N/A
0286
0287
Average Phase Voltage (High)
Average Phase Voltage (Low)
--- --- V F3 N/A
0288
0289
Voltage Vab (High)
Voltage Vab (Low)
--- --- V F3 N/A
028A
028B
Voltage Vbc (High)
Voltage Vbc (Low)
--- --- V F3 N/A
028C
028D
Voltage Vca (High)
Voltage Vca (Low)
--- --- V F3 N/A
028E
028F
Average Line Voltage (High)
Average Line Voltage (Low)
--- --- V F3 N/A
0290 Voltage Unbalance --- --- 0.1 x % F1 N/A
0291
0292
Voltage Van - Minimum (high)
Voltage Van - Minimum (Low)
--- --- V F3 N/A
0293
0294
Voltage Vbn - Minimum (high)
Voltage Vbn - Minimum (Low)
--- --- V F3 N/A
0295
0296
Voltage Vcn - Minimum (high)
Voltage Vcn - Minimum (Low)
--- --- V F3 N/A
0297
0298
Voltage Vab - Minimum (high)
Voltage Vab - Minimum (Low)
--- --- V F3 N/A
0299
029A
Voltage Vbc - Minimum (high)
Voltage Vbc - Minimum (Low)
--- --- V F3 N/A
029B
029C
Voltage Vca - Minimum (high)
Voltage Vca - Minimum (Low)
--- --- V F3 N/A
029D Voltage Unbalance - Minimum --- --- 0.1 x% F1 N/A
029E
029F
Voltage Van - Maximum (high)
Voltage Van - Maximum (Low)
--- --- V F3 N/A
02A0
02A1
Voltage Vbn - Maximum (high)
Voltage Vbn - Maximum (Low)
--- --- V F3 N/A
02A2
02A3
Voltage Vcn - Maximum (high)
Voltage Vcn - Maximum (Low)
--- --- V F3 N/A
02A4
02A5
Voltage Vab - Maximum (high)
Voltage Vab - Maximum (Low)
--- --- V F3 N/A
02A6
02A7
Voltage Vbc - Maximum (high)
Voltage Vbc - Maximum (Low)
--- --- V F3 N/A
02A8
02A9
Voltage Vca - Maximum (high)
Voltage Vca - Maximum (Low)
--- --- V F3 N/A
Table 7–10: PQM Memory Map (Sheet 8 of 55)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only