EasyManua.ls Logo

GE Multilin PQM - 7.3.3 PQM Memory Map (Sheet 47 of 55)

GE Multilin PQM
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 7: MODBUS COMMUNICATIONS MODBUS MEMORY MAP
PQM POWER QUALITY METER – INSTRUCTION MANUAL 7–63
TOTAL
HARMONIC
DISTORTION
ALARMS
1148 Average Current THD Relay 0 to 4 1 --- F29 0=OFF
1149 Average Current THD Level 5 to 1000 5 0.1 x % F1 100=10.0%
114A Average Current THD Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
114B Average Voltage THD Relay 0 to 4 1 --- F29 0=OFF
114C Average Voltage THD Level 5 to 1000 5 0.1 x % F1 100=10.0%
114D Average Voltage THD Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
114E Reserved
to
1157 Reserved
FREQUENCY
ALARMS
1158 Underfrequency Relay 0 to 4 1 --- F29 0=OFF
1059 Underfrequency Level 2000 to
7000
1 0.01 x Hz F1 40.00 Hz
115A Underfrequency Delay 1 to 100 1 0.1 x s F1 100=10.0 s
115B Zero Frequency Detect 0 to 1 1 --- F11 0=DISABLE
115C Overfrequency Relay 0 to 4 1 --- F29 0=OFF
115D Overfrequency Level 2000 to
12500
1 0.01 x Hz F1 70.00 Hz
115E Overfrequency Delay 1 to 100 1 0.1 x s F1 100=10.0 s
115F Reserved
to
1166 Reserved
POWER
ALARMS
1167 Power Alarms Level Base Units 0 to 1 1 --- F114 0=kW/kVAR
1168 Positive Real Power Relay 0 to 4 1 --- F29 0=OFF
1169 Positive Real Power Level in kW 1 to 65000 1 kW F1 1000 kW
116A Positive Real Power Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
116B Negative Real Power Relay 0 to 4 1 --- F29 0=OFF
116C Negative Real Power Level in kW 1 to 65000 1 kW F1 1000 kW
116D Negative Real Power Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
116E Positive Reactive Power Relay 0 to 4 1 --- F29 0=OFF
116F Positive Reactive Power Level in kVAR 1 to 65000 1 kVAR F1 1000 kVAR
1170 Positive Reactive Power Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
1171 Negative Reactive Power Relay 0 to 4 1 --- F29 0=OFF
1172 Negative Reactive Power Level in kVAR 1 to 65000 1 kVAR F1 1000 kVAR
1173 Negative Reactive Power Delay 5 to 6000 5 0.1 x s F1 100=10.0 s
1174 Positive Real Power Level in MW 1 to 65000 1 0.01 MW F1 10.00MW
1175 Negative Real Power Level in MW 1 to 65000 1 0.01 MW F1 10.00MW
1176 Positive Reactive Power Level in MVAR 1 to 65000 1 0.01 MVAR F1 10.00MVAR
1177 Negative Reactive Power Level in MVAR 1 to 65000 1 0.01 MVAR F1 10.00MVAR
Table 7–10: PQM Memory Map (Sheet 47 of 55)
GROUP ADDR
(HEX)
DESCRIPTION RANGE STEP
VALUE
UNITS and
SCALE
FORMAT FACTORY
DEFAULT
Notes:* Data type depends on the Command Operation Code.** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents OFF.**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.****** Applicable to older revisions with VFD display only
Courtesy of NationalSwitchgear.com