CHAPTER 2: INSTALLATION ELECTRICAL
PQM POWER QUALITY METER – INSTRUCTION MANUAL 2–17
Each switch input can be programmed with a 20-character user defined name and can be 
selected to accept a normally open or normally closed switch. A list of various functions 
that are assignable to switches is shown below, followed by a description of each function.
• ALARM RELAY: When a switch input is assigned to the alarm relay, a change in the 
switch status produces an alarm condition and the alarm relay activates. 
• PULSE INPUT 1 / 2 / 3 / 4: When a switch input is assigned as a pulse input counter, 
the PQM counts the number of transitions from open to closed when the input is 
configured as normally open and closed to open when the input is configured as 
normally closed. The minimum pulse width required for the PQM to read the switch is 
150 ms. Therefore, for the PQM to read one pulse, the switch input must be in its 
inactive state (closed/open) for a minimum of 150 ms then in its active state (open/
closed) for another 150 ms. See Section 1.3: Specifications on page –13 for more 
details.
• NEW DEMAND PERIOD: The PQM can be used for load shedding by assigning a switch 
input to a new demand period. This allows the PQM demand period to be 
synchronized with the utility meter. One of the billing parameters used by a utility is 
peak demand. By synchronizing the PQM to the utility meter, the PQM can monitor the 
demand level read by the utility meter and perform load shedding to prevent the 
demand from reaching the penalty level. The utility meter provides a dry contact 
output which can be connected to one of the PQM switch inputs. When the PQM 
senses a contact closure, it starts a new demand period (with Block Interval Demand 
calculation only).
• SETPOINT ACCESS: The access terminals must be shorted together in order for the 
faceplate keypad to have the ability to store new setpoints. Typically the access 
terminals are connected to a security keyswitch to allow authorized access only. Serial 
port commands to store new setpoints operate even if the access terminals are not 
shorted. When the access terminals are open, all actual and setpoint values can still 
be accessed for viewing; however, if an attempt is made to store a new setpoint value, 
the message SETPOINT ACCESS DISABLED
 is displayed and the previous setpoint 
remains intact. In this way, all of the programmed setpoints remain secure and 
tamper proof.
• SELECT ANALOG OUTPUT: This switch selection allows each analog output to be 
multiplexed into two outputs. If the switch is active, the parameter assigned in 
setpoint 
S2 SYSTEM SETUP \ ANALOG OUTPUT 1 \ ANALOG OUTPUT 1 ALT 
determines the output level. If the switch is not active, the parameter assigned in 
setpoint 
S2 SYSTEM SETUP \ ANALOG OUTPUT 1 \ ANALOG OUTPUT 1 MAIN is 
used. See Sections 2.2.7: Analog Outputs (Optional) below and 4.3.2: Analog Outputs 
on page –24 for additional details.
• SELECT ANALOG INPUT: This switch selection allows the analog input to be 
multiplexed into two inputs. If the switch is active, the parameter assigned in setpoint 
S2 SYSTEM SETUP \ ANALOG INPUT ALT is used to scale the input. If the switch is 
OFF ALARM RELAY NEW DEMAND PERIOD
SETPOINT ACCESS SELECT ANALOG OUTPUT  SELECT ANALOG INPUT 
AUX1 RELAY AUX2 RELAY AUX3 RELAY
PULSE INPUT 1 PULSE INPUT 2 PULSE INPUT 3
PULSE INPUT 4 CLEAR ENERGY CLEAR DEMAND
Courtesy of NationalSwitchgear.com