CHAPTER 4: PROGRAMMING S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL 4–27
Table 4–3: Analog Output Parameters
PARAMETER RANGE STEP PARAMETER RANGE STEP
Phase A Current 0 to 150% 1% Phase B kVA 0 to 65400 1 kVA
Phase B Current 0 to 150% 1% Phase C PF
0.01 lead to 0.01
lag
0.01
Phase C Current 0 to 150% 1% Phase C kW
–32500 to
+32500
1 kW
Neutral Current 0 to 150% 1% Phase C kvar
–32500 to
+32500
1 kvar
Average Phase
Current
0 to 150% 1% Phase C kVA 0 to 65400 1 kVA
Current Unbalance 0 to 100.0% 0.1% 3 Phase +kWh Used 0 to 65400 1 kWh
Voltage Van 0 to 200% 1% 3 Phase +kvarh Used 0 to 65400 1 kvarh
Voltage Vbn 0 to 200% 1% 3 Phase –kWh Used 0 to 65400 1 kWh
Voltage Vcn 0 to 200% 1% 3 Phase –kvarh Used 0 to 65400 1 kvarh
Voltage Vab 0 to 200% 1% 3 Phase kVAh Used 0 to 65400 1 kVAh
Voltage Vbc 0 to 200% 1%
Ph. A Current
Demand
0 to 7500 1 A
Voltage Vca 0 to 200% 1%
Ph. B Current
Demand
0 to 7500 1 A
Average Phase
Voltage
0 to 200% 1%
Ph. C Current
Demand
0 to 7500 1 A
Average Line Voltage 0 to 200% 1%
Neutral Current
Demand
0 to 7500 1 A
Voltage Unbalance 0 to 100.0% 0.1% 3 Phase kW Demand
–32500 to
+32500
1 kW
Frequency 00.00 to 75.00 Hz 0.01 Hz 3 Phase kvar Demand
–32500 to
+32500
1 kvar
3 Phase PF
0.01 lead to 0.01
lag
0.01 3 Phase kVA Demand 0 to 65400 1 kVA
3 Phase kW
–32500 to
+32500
1 kW 3 Phase Current THD 0.0 to 100% 0.1%
3 Phase kvar
–32500 to
+32500
1 kvar 3 Phase Voltage THD 0.0 to 100% 0.1%
3 Phase kVA 0 to 65400 1 kVA Phase A Current THD 0.0 to 100% 0.1%
3 Phase MW
–3250.0 to
+3250.0
0.1 MW Phase B Current THD 0.0 to 100% 0.1%
3 Phase Mvar
–3250.0 to
+3250.0
0.1 Mvar Phase C Current THD 0.0 to 100% 0.1%
Courtesy of NationalSwitchgear.com