CHAPTER 4: PROGRAMMING S2 SYSTEM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL 4–35
FIGURE 4–19: Setpoints Page 2 – System Setup / Pulse Input
PULSE INPUT UNITS: This message allows the user to input a user defined 10
character alphanumeric unit for the pulse inputs (i.e. kWh). The unit will be used by all
pulse inputs including the totalized value.
To enter the unit, perform the following steps:
1. Allow access to setpoints by enabling setpoint access.
2. Select the
PULSE INPUT UNITS message under the subgroup
S2 SYSTEM SETUP \ PULSE INPUT.
3. Use the and keys to change the blinking character
over the cursor. A space is selected like a character.
4. Press the key to store the character and advance the cursor to the
next position. To skip over a character press the key.
5. Continue entering characters and spaces until the desired message is
displayed. If a character is entered incorrectly, press the key
repeatedly until the cursor returns to the position of the error, and re-enter the
character.
PULSE INPUT 1 VALUE: Enter a value in this setpoint that will be equivalent to 1 pulse
input on the switch input assigned to PULSE INPUT 1 (i.e. 1 pulse = 100 kWh). The
accumulated value is displayed in actual values under
A1 METERING\PULSE INPUT
COUNTERS\PULSE INPUT 1
.
PULSE INPUT 2 VALUE: Enter a value in this setpoint that will be equivalent to 1 pulse
input on the switch input assigned to PULSE INPUT 2 (i.e. 1 pulse = 100 kWh). The
accumulated value is displayed in actual values under
A1 METERING\PULSE INPUT
COUNTERS\PULSE INPUT 2
.
PULSE INPUT 3 VALUE: Enter a value in this setpoint that will be equivalent to 1 pulse
input on the switch input assigned to PULSE INPUT 3 (i.e. 1 pulse = 100 kWh). The
accumulated value is displayed in actual values under
A1 METERING\PULSE INPUT
COUNTERS\PULSE INPUT 3
.
PULSE INPUT 4 VALUE: Enter a value in this setpoint that will be equivalent to 1 pulse
input on the switch input assigned to PULSE INPUT 4 (i.e. 1 pulse = 100 kWh). The
accumulated value is displayed in actual values under
A1 METERING\PULSE INPUT
COUNTERS\PULSE INPUT 4
.
PULSE INPUT TOTAL: This setpoint allows the user to define which pulse inputs are to
be added together. For example, if the selection is this setpoint is 1+2+3, the PULSE
INPUT 1, PULSE INPUT 2 and PULSE INPUT 3 values shown in
A1 METERING \ PULSE
COUNTERS \ PULSE INPUT 1/2/3/4
will be added together and displayed in
A1:METERING \ PULSE INPUT COUNTERS \ PULSE IN 1+2+3.
VALUE VALUE
STORE
STORE
STORE