EasyManuals Logo

GE T60 User Manual

GE T60
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #251 background imageLoading...
Page #251 background image
GE Multilin T60 Transformer Protection System 5-117
5 SETTINGS 5.4 SYSTEM SETUP
5
h) DIFFERENTIAL AND RESTRAINT CURRENT CALCULATIONS
Differential and restraint currents are calculated as follows:
(EQ 5.21)
(EQ 5.22)
(EQ 5.23)
(EQ 5.24)
(EQ 5.25)
(EQ 5.26)
where , , and are the phase differential currents and , , and are the phase restraint currents.
i) TRANSFORMER WINDINGS BETWEEN TWO BREAKERS
When the relay is to protect a transformer with windings connected between two breakers, such as in a ring bus or breaker-
and-a-half station configuration, one of the methods for configuring currents into the relay presented below should be used
(see the Breaker-and-a-Half Scheme diagram in the Overview section of this chapter).
For this example it is assumed that winding 1 is connected between two breakers and winding 2 is connected to a single
breaker. The CTs associated with winding 1 are CTX, at 1200/5 A and CTY, at 1000/5 A. CTX is connected to current input
channels 1 through 3 inclusive and CTY is connected to current input channels 5 through 7 inclusive on a type 8H CT/VT
module in relay slot “F.” The CT2 on winding 2 is 5000/5 A and is connected to current input channels 1 through 4 inclusive
on a type 8F CT/VT module in relay slot “M”.
SETUP METHOD A (PREFERRED)
This approach is preferred because it provides increased sensitivity as the current from each individual set of CTs partici-
pates directly in the calculation of CT ratio mismatch, phase compensation, zero-sequence removal (if required) and the
differential restraint current. The concept used in this approach is to consider that each set of CTs connected to winding 1
represents a connection to an individual winding. For our example we consider the two-winding transformer to be a three-
winding transformer.
1. Enter the settings for each set of CTs in the
SYSTEM SETUP AC INPUTS CURRENT BANK settings menu.
PHASE CT F1 PRIMARY: “1200 A”
PHASE CT F1 SECONDARY: “5 A”
GROUND CT F1 PRIMARY: “1 A” (default value)
GROUND CT F1 SECONDARY: “1 A” (default value)
PHASE CT F5 PRIMARY: “1000 A”
PHASE CT F5 SECONDARY: “5 A”
GROUND CT F5 PRIMARY: “1 A” (default value)
GROUND CT F5 SECONDARY: “1 A” (default value)
PHASE CT M1 PRIMARY: “5000 A”
PHASE CT M1 SECONDARY: “5 A”
GROUND CT M5 PRIMARY: “5000 A”
GROUND CT M5 SECONDARY: “5 A”
2. Configure source n (source 1 for this example) as the current from CTX in Winding 1 in the
SYSTEM SETUP  SIGNAL
SOURCES
 SOURCE 1(4) settings menu.
SOURCE 1 NAME: “WDG 1X”
SOURCE 1 PHASE CT: “F1”
SOURCE 1 GROUND CT: “None”
SOURCE 1 PHASE VT: “None”
SOURCE 1 AUX VT: “None”
Id
A
I
A
c
1 I
A
c
2 I
A
c
w
total
+++=
Id
B
I
B
c
1 I
B
c
2 I
B
c
w
total
+++=
Id
C
I
C
c
1 I
C
c
2 I
C
c
w
total
+++=
Ir
A
max I
A
c
1 I
A
c
2I
A
c
w
total
=
Ir
B
max I
B
c
1 I
B
c
2I
B
c
w
total
=
Ir
C
max I
C
c
1 I
C
c
2I
C
c
w
total
=
Id
A
Id
B
Id
C
Ir
A
Ir
B
Ir
C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE T60 and is the answer not in the manual?

GE T60 Specifications

General IconGeneral
Frequency50/60 Hz
MountingPanel Mount
Protection FunctionsOvercurrent
Communication ProtocolsDNP3
Operating Temperature+70°C
EnclosureIP54 (front panel)

Related product manuals