EasyManua.ls Logo

GE T60

GE T60
770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-118 T60 Transformer Protection System GE Multilin
5.4 SYSTEM SETUP 5 SETTINGS
5
3. Configure source n (source 2 for this example) as the current from CTY in Winding 1 in the SYSTEM SETUP  SIGNAL
SOURCES  SOURCE 1(4) settings menu.
SOURCE 2 NAME: “WDG 1Y”
SOURCE 2 PHASE CT: “F5”
SOURCE 2 GROUND CT: “None”
SOURCE 2 PHASE VT: “None”
SOURCE 2 AUX VT: “None”
4. Configure source n (source 3 for this example) to be used as the current in Winding 2 in the SYSTEM SETUP  SIGNAL
SOURCES  SOURCE 1(4) settings menu.
SOURCE 3 NAME: “WDG 2"
SOURCE 3 PHASE CT: “M1”
SOURCE 3 GROUND CT: “M1”
SOURCE 3 PHASE VT: “None”
SOURCE 3 AUX VT: “None”
5. Configure the source setting of the transformer windings in the SYSTEM SETUP  TRANSFORMER  WINDING n set-
tings menu.
WINDING 1 SOURCE: “WDG 1X”
WINDING 2 SOURCE: “WDG 1Y”
WINDING 3 SOURCE: “WDG 2"
SETUP METHOD B (ALTERNATE)
This approach adds the current from each phase of the CT1 and CT2 together to represent the total winding 1 current. The
procedure is shown below.
1. Enter the settings for each set of CTs in the
SYSTEM SETUP AC INPUTS CURRENT BANK settings menu, as shown for
Method A above.
2. Configure Source n (Source 1 for this example) to be used as the summed current in Winding 1 in the SYSTEM SETUP
 SIGNAL SOURCES  SOURCE n settings menu.
SOURCE 1 NAME: “WDG 1"
SOURCE 1 PHASE CT: “F1 + F5”
SOURCE 1 GROUND CT: “None”
SOURCE 1 PHASE VT: “None”
SOURCE 1 AUX VT: “None”
3. Configure Source n (Source 2 for this example) to be used as the Winding 2 current in the SYSTEM SETUP  SIGNAL
SOURCES  SOURCE n settings menu.
SOURCE 2 NAME: “WDG 2"
SOURCE 2 PHASE CT: “M1”
SOURCE 2 GROUND CT: “M1”
SOURCE 2 PHASE VT: “None”
SOURCE 2 AUX VT: “None”

Table of Contents

Related product manuals