GE Multilin T60 Transformer Protection System 5-143
5 SETTINGS 5.4 SYSTEM SETUP
5
c) PMU CALIBRATION
PATH: SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1 CALIBRA-
TION
This menu contains user angle and magnitude calibration data for the phasor measurement unit (PMU). This data is com-
bined with the factory adjustments to shift the phasors for better accuracy.
PMU 1 VA... IG CALIBRATION ANGLE: These settings recognize applications with protection class voltage and cur-
rent sources, and allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter
a positive correction of the secondary signal lags the true signal; and negative value if the secondary signal leads the
true signal.
PMU 1
CALIBRATION
PMU 1 VA CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VA CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 VB CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VB CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 VC CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VC CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 VX CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 VX CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IA CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IA CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IB CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IB CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IC CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IC CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 IG CALIBRATION
ANGLE: 0.00°
Range: –5.00 to 5.00° in steps of 0.05
MESSAGE
PMU 1 IG CALIBRATION
MAG: 100.0%
Range: 95.0 to 105.0 in steps of 0.1%
MESSAGE
PMU 1 SEQ VOLT SHIFT
ANGLE: 0°
Range: –180 to 180° in steps of 30
MESSAGE
PMU 1 SEQ CURR SHIFT
ANGLE: 0°
Range: –180 to 180° in steps of 30

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE T60 and is the answer not in the manual?

GE T60 Specifications

General IconGeneral
Frequency50/60 Hz
MountingPanel Mount
Protection FunctionsOvercurrent
Communication ProtocolsDNP3
Operating Temperature+70°C
EnclosureIP54 (front panel)

Related product manuals