GE Multilin T60 Transformer Protection System 5-327
5 SETTINGS 5.8 INPUTS AND OUTPUTS
5
• UINTEGER 1 DEFAULT: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the UINTEGER 1 DEFAULT MODE is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
• UINTEGER 1 DEFAULT MODE: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the
UINTEGER 1 DEFAULT setting.
The GOOSE integer input FlexInteger values are available for use in other T60 functions that use FlexInteger values.