7-2 T60 Transformer Protection System GE Multilin
7.1 COMMANDS 7 COMMANDS AND TARGETS
7
7.1.3 CLEAR RECORDS
PATH: COMMANDS  CLEAR RECORDS
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a com-
mand setting to “Yes” and pressing the ENTER key. After clearing data, the command setting automatically reverts to “No”.
The CLEAR ALL RELAY RECORDS command does not clear the XFMR LIFE LOST (transformer loss of life) value.
7.1.4 SET DATE AND TIME
PATH: COMMANDS  SET DATE AND TIME
The date and time can be entered on the faceplate keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER key is pressed.
 COMMANDS
 CLEAR RECORDS
CLEAR USER FAULT
REPORTS? No
Range: No, Yes
CLEAR EVENT RECORDS?
No
Range: No, Yes
CLEAR OSCILLOGRAPHY?
No
Range: No, Yes
CLEAR DATA LOGGER?
No
Range: No, Yes
CLEAR BREAKER 1
ARCING AMPS? No
Range: No, Yes
CLEAR BREAKER 2
ARCING AMPS? No
Range: No, Yes
CLEAR DEMAND
RECORDS?: No
Range: No, Yes
CLEAR ENERGY?
No
Range: No, Yes
CLEAR UNAUTHORIZED
ACCESS? No
Range: No, Yes
CLEAR DIRECT I/O
COUNTERS? No
Range: No, Yes. Valid only for units with Direct Input/
Output module.
CLEAR PMU 1 RECORDS?
No
Range: No, Yes
CLEAR PMU 1 CONFIG
CHANGE COUNTER? No
Range: No, Yes
CLEAR LOSS OF LIFE
RECORDS? No
Range: No, Yes
CLEAR TELEPROTECT
COUNTERS? No
Range: No, Yes
CLEAR ALL RELAY
RECORDS? No
Range: No, Yes
 COMMANDS
 SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
(YYYY/MM/DD HH:MM:SS)
NOTE