B-44 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
65D1 Power Swing Detect Trip Mode 0 to 1 --- 1 F514 0 (Delayed)
65D2 Power Swing Detect Block 0 to 4294967295 --- 1 F300 0
65D4 Power Swing Detect Target 0 to 2 --- 1 F109 0 (Self-reset)
65D5 Power Swing Detect Event 0 to 1 --- 1 F102 0 (Disabled)
65D6 Power Swing Detect Shape 0 to 1 --- 1 F085 0 (Mho Shape)
65D7 Power Swing Detect Quad Forward Middle 0.1 to 500 ohms 0.01 F001 6000
65D8 Power Swing Detect Quad Forward Outer 0.1 to 500 ohms 0.01 F001 7000
65D9 Power Swing Detect Quad Reverse Middle 0.1 to 500 ohms 0.01 F001 6000
65DA Power Swing Detect Quad Reverse Outer 0.1 to 500 ohms 0.01 F001 7000
65DB Power Swing Detect Outer Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DC Power Swing Detect Outer Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DD Power Swing Detect Middle Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65DE Power Swing Detect Middle Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65DF Power Swing Detect Inner Right Blinder 0.1 to 500 ohms 0.01 F001 10000
65E0 Power Swing Detect Inner Left Blinder 0.1 to 500 ohms 0.01 F001 10000
65E1 Power Swing I2 Supervision Enable 0 to 4294967295 --- 1 F300 0
65E3 Power Swing I2 Supervision 0.05 to 30 pu 0.001 F001 200
Load Encroachment (Read/Write Grouped Setting)
66C0 Load Encroachment Function 0 to 1 --- 1 F102 0 (Disabled)
66C1 Load Encroachment Source 0 to 5 --- 1 F167 0 (SRC 1)
66C2 Load Encroachment Minimum Voltage 0 to 3 pu 0.001 F001 250
66C3 Load Encroachment Reach 0.02 to 250 ohms 0.01 F001 100
66C4 Load Encroachment Angle 5 to 50 degrees 1 F001 30
66C5 Load Encroachment Pickup Delay 0 to 65.535 s 0.001 F001 0
66C6 Load Encroachment Reset Delay 0 to 65.535 s 0.001 F001 0
66C7 Load Encroachment Block 0 to 4294967295 --- 1 F300 0
66C9 Load Encroachment Target 0 to 2 --- 1 F109 0 (Self-reset)
66CA Load Encroachment Events 0 to 1 --- 1 F102 0 (Disabled)
66CB Reserved (6 items) 0 to 65535 --- 1 F001 0
Phase Undervoltage (Read/Write Grouped Setting) (3 Modules)
7000 Phase Undervoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7001 Phase Undervoltage 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)
7002 Phase Undervoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7003 Phase Undervoltage 1 Curve 0 to 1 --- 1 F111 0 (Definite Time)
7004 Phase Undervoltage 1 Delay 0 to 600 s 0.01 F001 100
7005 Phase Undervoltage 1 Minimum Voltage 0 to 3 pu 0.001 F001 100
7006 Phase Undervoltage 1 Block 0 to 4294967295 --- 1 F300 0
7008 Phase Undervoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7009 Phase Undervoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
700A Phase Undervoltage 1 Measurement Mode 0 to 1 --- 1 F186 0 (Phase to
Ground)
700B Reserved (6 items) 0 to 1 --- 1 F001 0
7011 ...Repeated for Phase Undervoltage 2
7022 ...Repeated for Phase Undervoltage 3
Phase Overvoltage (Read/Write Grouped Setting) (3 Modules)
7040 Phase Overvoltage 1 Function 0 to 1 --- 1 F102 0 (Disabled)
7041 Phase Overvoltage 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
7042 Phase Overvoltage 1 Pickup 0 to 3 pu 0.001 F001 1000
7043 Phase Overvoltage 1 Delay 0 to 600 s 0.01 F001 100
7044 Phase Overvoltage 1 Reset Delay 0 to 600 s 0.01 F001 100
7045 Phase Overvoltage 1 Block 0 to 4294967295 --- 1 F300 0
7047 Phase Overvoltage 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7048 Phase Overvoltage 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7049 ...Repeated for Phase Overvoltage 2
Table B–10: MODBUS MEMORY MAP (Sheet 36 of 74)