B-64 T60 Transformer Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
B39D ...Repeated for module number 16
B3A0 ...Repeated for module number 17
B3A3 ...Repeated for module number 18
B3A6 ...Repeated for module number 19
B3AC ...Repeated for module number 20
B3AF ...Repeated for module number 22
B3B2 ...Repeated for module number 23
B3B5 ...Repeated for module number 24
IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)
B400 Number of Status Indications in GGIO1 8 to 128 --- 8 F001 8
B402 IEC 61850 GGIO1 Indication FlexLogic operands (128
items)
0 to 4294967295 --- 1 F300 0
IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 Modules)
B5A0 IEC 61850 Configurable GOOSE Function 0 to 1 --- 1 F102 0 (None)
B5A1 IEC 61850 Configurable GOOSE ID --- --- --- F209 “GOOSEOut_x_”
B5C2 Configurable GOOSE Destination MAC Address --- --- --- F072 0
B5C5 IEC 61850 Configurable GOOSE VLAN Transmit Priority 0 to 7 --- 1 F001 4
B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 --- 1 F001 0
B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0
B5C8 IEC 61850 Configurable GOOSE ConfRev 1 to 4294967295 --- 1 F003 1
B5CA IEC 61850 Configurable GOOSE Retransmission Curve 0 to 3 --- 1 F611 3 (Relaxed)
B5CB Configurable GOOSE dataset items for transmission
(64 items)
0 to 1008 --- 1 F616 0 (None)
B60B ...Repeated for Module 2
B676 ...Repeated for Module 3
B6E1 ...Repeated for Module 4
B74C ...Repeated for Module 5
B7B7 ...Repeated for Module 6
B822 ...Repeated for Module 7
B88D ...Repeated for Module 8
IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (16 Modules)
B900 Configurable GOOSE dataset items for reception
(32 items)
0 to 197 --- 1 F233 0 (None)
B920 ...Repeated for Module 2
B940 ...Repeated for Module 3
B960 ...Repeated for Module 4
B980 ...Repeated for Module 5
B9A0 ...Repeated for Module 6
B9C0 ...Repeated for Module 7
B9E0 ...Repeated for Module 8
BA00 ...Repeated for Module 9
BA20 ...Repeated for Module 10
BA40 ...Repeated for Module 11
BA60 ...Repeated for Module 12
BA80 ...Repeated for Module 13
BAA0 ...Repeated for Module 14
BAC0 ...Repeated for Module 15
BAE0 ...Repeated for Module 16
Contact Inputs (Read/Write Setting) (96 Modules)
BB00 Contact Input 1 Name --- --- --- F205 “Cont Ip 1“
BB06 Contact Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
BB07 Contact Input 1 Debounce Time 0 to 16 ms 0.5 F001 20
BB08 ...Repeated for Contact Input 2
BB10 ...Repeated for Contact Input 3
BB18 ...Repeated for Contact Input 4
Table B–10: MODBUS MEMORY MAP (Sheet 56 of 74)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT