ADV200 • Functions description and parameters list 155
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
23.8.6 5714FLfaultenablesrc LINK 16 6002 0 16384 ERW FVS
This parameter is used to select the origin (source) of the FLfaultenable signal.
The signal to be associated with this function can be selected from the “L_DIGSEL1” selection list.
0 FLfaultenable not active (No FastLink alarm signal)
1 FLfaultenable active (FastLink alarm signal)
When the drive detects a FastLink fault, it prepares to trigger a “FastLink fault” alarm.
This command is used to select whether an alarm is generated when a fault is detected.
Alarm generation is enabled in the default conguration.
The conguration of the “FLfaultenablesrc” parameter can be changed to control the phases in which alarm
generation is enabled.
For example, by connecting the “FLfaultenablesrc” parameter to “Enablestatemon” you can enable gen-
eration of the “FastLink fault” alarm in the phase when the drive is enabled.
In systems where drive the drives are not powered-off simultaneously, some drives detect a FastLink fault and
generate a FastLink alarm.
This parameter is used to disable the alarm at power-off by connecting the “FLfaultenablesrc” parameter to
“Enablestatemon”.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
23.8.7 5730FLFwd1src LINK 16/32BIT 6000 0 16384 ERW FVS
23.8.8 5732FLFwd2src LINK 16/32BIT 6000 0 16384 ERW FVS
23.8.9 5734FLFwd3src LINK 16/32BIT 6000 0 16384 ERW FVS
23.8.10 5736FLFwd4src LINK 16/32BIT 6000 0 16384 ERW FVS
This parameter is used to select the origin (source) of the FLFw1src signal.
The signal to be associated with this function can be selected from the “L_FLWORD” selection list.
On the drive congured as the master, these parameters are used to select the data to be sent to the rst
slave.
On drives congured as slaves, these paramters are used to select the data that the slave must include in the
data frame to replace the data received from the previous drive.
Replacement is disabled in the default conguration. It can be enabled with the PAR 5712 “FLNFwdslave
chg“ parameter.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
23.8.11 5830FLRev1src LINK 16/32BIT 6000 0 16384 ERW FVS
23.8.12 5832FLRev2src LINK 16/32BIT 6000 0 16384 ERW FVS
Parameter signicant only for Slave drive, indicates what data to insert in rst word to be sent to Master drive
when Slave is interrogated. Selectable values are shown on the L_FLWORD list.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
23.8.13 5750FLFwd1mon INT32 32BIT 0 0 2^32 ER FVS
23.8.14 5752FLFwd2mon INT32 32BIT 0 0 2^32 ER FVS
23.8.15 5754FLFwd3mon INT32 32BIT 0 0 2^32 ER FVS
23.8.16 5756FLFwd4mon INT32 32BIT 0 0 2^32 ER FVS
23.8.17 5758FLFwd5mon INT32 32BIT 0 0 2^32 ER FVS
23.8.18 5760FLFwd6mon INT32 32BIT 0 0 2^32 ER FVS
23.8.19 5762FLFwd7mon INT32 32BIT 0 0 2^32 ER FVS
23.8.20 5764FLFwd8mon INT32 32BIT 0 0 2^32 ER FVS
These parameters are not used on the master drive.
On the slave drive these parameters show the value received from the previous drive. The “Inv” parameters en-
able the value received to be used with the opposite sign, without changing any of the data sent to subsequent
slaves.