ADV200 Functions description and parameters list 167
35 Plc3 fault
36 Plc4 fault
37 Plc5 fault
38 Plc6 fault
39 Plc7 fault
40 Plc8 fault
41 Watchdog
42 Trap error
43 System error
44 User error
45 Param error
46 Load def par
47 Plc cfg error
48 Load def plc
49 Key failed
50 Encoder error
51 Opt cfg change
52 Not Used3
53 Plc9 fault
54 Plc10 fault
55 Plc11 fault
56 Plc12 fault
57 Plc13 fault
58 Plc14 fault
59 Plc15 fault
60 Plc16 fault
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.60 4720Almautoresettime s FLOAT 0.0 0.0 60.0 ERW FVS
Setting of the time interval that must pass before executing an automatic reset.
If no alarms are enabled the drive is set to restart.
If some alarms are still enabled the drive is set to execute a new attempt at automatic reset.
At each attempted reset a counter increases. If the limit set in the Alm autoreset number parameter is reached
the drive is set to make no more attempts at reset and waits for a user reset.
The counter is set to zero when an automatic reset or user reset is performed and no alarms are enabled.
If the parameter is 0 the function is disabled.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
24.61 4722Almautoresetnumber UINT16 20 0 100 ERW FVS
Setting of the maximum number of attempted automatic resets.

Table of Contents

Other manuals for gefran ADV200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran ADV200 and is the answer not in the manual?

gefran ADV200 Specifications

General IconGeneral
Brandgefran
ModelADV200
CategoryInverter
LanguageEnglish

Related product manuals