ADV200 • Functions description and parameters list 175
0 Threshold not exceeded
1 Threshold exceeded
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4372DS402statusword UINT16 16 0 0 65535 ER
This parameter displays the status word according to the DS402 prole. For more information reference should
be made to the eldbus manual.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4394PFdrvstatusword1 UINT16 16 0 0 65535 ER
This parameter displays the status word 1 according to the Prodrives prole. For more information reference
should be made to the eldbus manual.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4396PFdrvstatusword2 UINT16 16 0 0 65535 ER
This parameter displays the status word 2 according to the Prodrives prole. For more information reference
should be made to the eldbus manual.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4538KTY84/PTCcurrent mA UINT32 2 1 10 ERWS
Value of current owing in connected temperature sensor KTY84.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4708Almdigoutmon1 BIT 16 0 0 1 ER
This signal is activated when the alarm congured in parameter 4700alarmdigsel1 is active.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4710Almdigoutmon2 BIT 16 0 0 1 ER
This signal is activated when the alarm congured in parameter 4702alarmdigsel2 is active.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4712Almdigoutmon3 BIT 16 0 0 1 ER
This signal is activated when the alarm congured in parameter 4704alarmdigsel3is active.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4714Almdigoutmon4 BIT 16 0 0 1 ER
This signal is activated when the alarm congured in parameter 4706alarmdigsel4 is active.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4770Firstalarm UINT32 16 0 0 0 ERW
This parameter displays the rst alarm to be activated.
0 No alarm
1 Overvoltage
2 Undervoltage
3 Ground fault
4 Overcurrent
5 Desaturation
6 MultiUndervolt
7 MultiOvercurr
8 MultiDesat
9 Heatsink OT