ADV200 • Functions description and parameters list 177
1 1 = PLC 2 fault active
2 1 = PLC 3 fault active
3 1 = PLC 4 fault active
4 1 = PLC 5 fault active
5 1 = PLC 6 fault active
6 1 = PLC 7 fault active
7 1 = PLC 8 fault active
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4840Alarmlostate UINT32 32 0 0 0 ER
This parameter displays the state of alarms 1..32 of the drive.
Bit Description
0 1 = Overvoltage active
1 1 = Undervoltage active
2 1 = Ground fault active
3 1 = Overcurrent active
4 1 = Desaturation active
5 1 – MultiUndervolt active
6 1 = MultiOvercurr active
7 1 – MultiDesat active
8 1 = Heatsink OT active
9 1 = Heatsink lin OT active
10 1 = Air OT active
11 1 = Motor OT active
12 1 = Drive overload active
13 1 = Motor overload active
14 1 = Bres overload active
15 1 = Phase loss active
16 1 = Opt bus fault active
17 1 = Opt 1 I/O fault active
18 1 = Opt 2 I/O fault active
19 1 = Opt enc fault active
20 1 = External fault active
21 1 = Fbk loss active
22 1 = Overspeed active
23 1 = Ref loss active
24 1 = Emg stop alarm active
25 1 = Power down active
26 1 = not used
27 1 = not used
28 1 = not used
29 1 = not used
30 1 = not used
31 1 = not used
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
4842Alarmhistate UINT32 32 0 0 0 ER
This parameter displays the state of alarms 33...64 of the drive.
Bit Description
0 1 = PLC 1 fault active
1 1 = PLC 2 fault active
2 1 = PLC 3 fault active
3 1 = PLC 4 fault active
4 1 = PLC 5 fault active
5 1 = PLC 6 fault active
6 1 = PLC 7 fault active