ADV200 • Troubleshooting 183
Code Errormessageshownon
thedisplay
Sub-code Description
0068H-104
The application that has been downloaded has a different Crc on the DataBlock and Func-
tion table.
0069H-105
A Trap error or System error has occurred.
The drive has automatically executed a Power-up operation.
Application not executed.
See the Alarm List for more information about an error that has occurred.
006AH-106
The application that has been downloaded has an invalid identification code (Task).
006BH-107
The application that has been downloaded uses an incorrect task number (Task).
006CH-108
The application that has been downloaded has an incorrect Crc (Tables + Code)
Solution:Remove the MDPLC application or download a correct MDPLC application.
48 Loaddefplc
Condition:this can occur during loading of the parameter database saved in the Flash memory of the
MDPLC application
it is normal if it appears the first time the drive is switched on, after downloading a new application. If this
message appears when the drive is already in use it means there has been a problem in the parameter
database saved in the Flash memory.
If this message appears the drive automatically runs the Load default command.
0001H-1 The database saved is not valid
Solution:Set the parameters to the desired value and run Save parameter.
49 Keyfailed
Condition:Shis may occur at drive power-on if the incorrect enabling key was inserted for a given firmware
function.
0001H-1 Incorrect PLC key. PLC application not available.
Solution:Ask Gefran for the correct key to enable the desired firmware function.
50 Encodererror
Condition: this condition may occur when the drive is powered during encoder setup each time parameter
552 Regulationmode is set.
100H-256
An error occurred during setup; the information received from the encoder is not reliable. If
the encoder is used for feedback the Speedfbkloss [22] alarm is also generated.
Solution: Take the recommended action for the Speedfbkloss [22] alarm.
200H-512
Cause: The firmware on the optional encoder card is incompatible with that on the regula-
tion card. The information received from the encoder is not reliable
Solution: Contact Gefran in order to update the firmware on the optional encoder card.
51 Optcfgchange
Condition: this may occur when powering the drive if an expansion card has been removed or replaced or
the incorrect enable key is inserted for a given firmware function.
0064H-100 Card removed from slot 1.
0014H-20 Card removed from slot 2
0003H-3 Card removed from slot 3
0078H-120 Card removed from slot 1 and from slot 2
0067H-103 Card removed from slot 1 and from slot 3.
0017H-23 Card removed from slot 2 and from slot 3.
007BH-123 Card removed from slot 1, from slot 2 and from slot 3
Solution: Check the hardware configuration, then press ESC. Save the parameters (Saveparameters,
menu 04.01 par 550) to save the new hardware configuration.
52
NotUsed3
53...60
Plc9fault
...
Plc16fault
Condition:Enabled application developed in the IEC 61131-3 environment has found the conditions for
generating this specific alarm to be true. The meaning of the alarm depends on the type of application. For
more information, refer to the documentation concerning the specific application..
XXXXH-X The XXXXH-X code indicates the reason for the error: make a note of this to discuss it with
the service centre.
Solution:Refer to the documentation concerning the enabled application.