ADV200 • Parameters List 257
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
1 Warning
2 Disable
3 Stop
4 Fast stop
24.24 4562 SpdFbkLoss holdoff ms UINT16 200 0 10000 RW FV_
24.25 4564 SpdFbkLoss threshold rpm INT16 100 5 CALCI RW FV_
24.26 4570 Drive ovld activity ENUM Ignore 0 4 ERW
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.27 4572 Motor ovld activity ENUM Warning 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.28 4574 Bres ovld activity ENUM Disable 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.29 4582 HTsens restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.30 4584 HTsens restart time ms UINT16 20000 120 60000 ERW FVS
24.31 4600 InAir activity ENUM Stop 0 4 ERW FVS
0 Ignore
1 Warning
2 Disable
3 Stop
4 Fast stop
24.32 4602 InAir restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.33 4604 InAir restart time ms UINT16 1000 120 30000 ERW FVS
24.34 4606 InAir holdoff ms UINT16 10000 0 30000 ERW FVS
24.35 4610 Desat restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.36 4612 Desat restart time ms UINT16 2000 1000 10000 ERW FVS
24.37 4620 IOverC restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.38 4622 IOverC restart time ms UINT16 2000 1000 10000 ERW FVS
24.39 4630 OverV restart ENUM Disable 0 1 ERW FVS
0 Disable
1 Enable
24.40 4632 OverV restart time ms UINT16 2000 1000 10000 ERW FVS
24.41 4640 UnderV restart ENUM Enable 0 1 ERW FVS
0 Disable
1 Enable