46 ADV200 • Functions description and parameters list
Currentthrmon is enabled. The signal is disabled when the motor speed falls below the threshold - the toler-
ance band. If the threshold value is lower than the value set in 982Currentthrhyster, the result produced is
always 0. The value set in this parameter is active in both directions of rotation.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
10.15 982 Currentthrhyster perc UINT16 0 0 100 RW FVS
Setting of the tolerance band around the current threshold. A value of 100% corresponds to the value of the
drive heavy duty continuous current, displayed in parameter 488Drivecontcurrent, when parameter 566
Driveoverloadmode is set to Heavyduty, and no derating of the drive continuous current has been activated
due to any modication of Mains voltage, Switching frequency and Ambient temperature.
The drive heavy duty continuous current value to be used is the factory setting read in PAR 488 Drivecont
current.
The tolerance band is the same for both directions of rotation of the motor.